Setting Command Signal Type

Code
Name
Modbus level / edge
E8.13
sensitivity selection
Setting range of E8.13:
E8.13 = 0: Level sensitive
The control word is not a real edge sensitive, master should manually reset the
command.
For example:
1. Simulate an error
2. Set bit 5 = 1, the error is reset
3. Simulate an error again
4. Set bit 5 = 1, the error is not reset
5. Master should set bit 5 = 0 firstly, then set bit 5 = 1, the error is reset
E8.13 = 1: Edge sensitive
The control command is reset automatically after the activation.
For example:
1. Simulate an error
2. Set bit 5 = 1, the error is reset
3. Simulate an error again
4. Set bit 5 = 1, the error is not reset

Setting Modbus transmission mode

Code
Name
Modbus transmission
E8.14
mode selection
Modbus ASCII inter-
E8.15
character timeout
E8.15 is used to set the maximum time delay allowed between 2 characters of a
single ASCII frame.
Setting range
0: Level sensitive
1: Edge sensitive
Setting range
0: RTU transmission
1: ASCII transmission
mode
1.0...5.0 s
Functions and Parameters
Default
Unit
1
Default
Unit
0
1.0
s