440/653
Functions and Parameters
12.22 H8: IO&IO Plus Card Parameters
12.22.1 IO & IO Plus Card Analog Input Configuration
This function is implemented to configure the external analog input EAI1 and
EAI2, which is provided in IO and IO plus extension card.
Code
Name
H8.05 EAI1 input mode
H8.06 EAI1 input polarity setting
H8.07 EAI1 dead zone filter value
H8.09 EAI1 filter time
H8.10 EAI1 gain
H8.15 EAI1 curve minimum
H8.16 EAI1 curve minimum value
H8.17 EAI1 curve maximum
H8.18 EAI1 curve maximum value
H8.30 EAI2 input mode
Bosch Rexroth AG R912005854_Edition 09
Rexroth Frequency Converter EFC x610
Setting range
Default
0: 0...20 mA
1: 4...20 mA
2: 0...10 V
3: 0...5 V
4: 2...10 V
5: -10...10 V
0: Polarity inactive
1: Polarity active
without direction
control
2: Polarity active
with direction con-
trol
0.0...30.0 %
0.000...2.000
0.100
0.00...10.00
1.00
-120.0 %...
[H8.17]
-[E0.09]...[E0.09]
0.00
Hz
[H8.15]...120.0 % 100.0
-[E0.09]...[E0.09]
50.00
Hz
0: 0...20 mA
1: 4...20 mA
2: 0...10 V
3: 0...5 V
4: 2...10 V
5: -10...10 V
Unit
Step
0
1
0.0
%
0.1
s
0.001
-
0.01
0.0
%
0.1
Hz
0.01
%
0.1
Hz
0.01
0
Series
Attri.
Stop
Stop
Run
Run
Run
Run
Run
Run
Run
Stop

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rexroth efc 3610Rexroth efc 5610