252/653
Functions and Parameters

12.10.3 Relay Output

This function defines the relay output for system state monitoring.
Code
Name
Relay 1 output selec-
E2.15
tion
DO1/relay1 output val-
ues from extension
E2.20
card fieldbus communi-
cation
Setting range of E2.15:
0: Converter ready
After power on, when no error happens, no run command, output active indi-
cates that the converter is ready for running.
1: Converter running
The output is active when the frequency converter is running and has fre-
quency output (including 0.00 Hz).
2: Converter DC-braking
The output is active when the converter is in the DC braking process at start-
ing or stopping process. See
page 210
and
chapter 12.8.9 "Stop Mode Configuration" on page
3: Converter running at zero speed
The output is active when the frequency converter is running at zero speed.
There is no output for this selection during dead zone time of rota-
tion direction change.
4: Speed arrival
This function is used to detect the difference between the output frequency
and the set frequency. The indicative signals are outputted when the differ-
ence between the output frequency and the set frequency is within the range
set in [E2.70], see
258.
5: Frequency level detection signal (FDT1)
6: Frequency level detection signal (FDT2)
See
chapter 12.10.5 "Frequency Detection Function" on page
7: Simple PLC stage complete
8: Simple PLC cycle complete
See
chapter 12.11 "E3: Multi-Speed and Simple PLC" on page
Bosch Rexroth AG R912005854_Edition 09
Setting range
0...25
Bit0: 0 (open collector
is opened); 1(open
collector is closed)
Bit8: 0 (Tb_Ta is
opened); 1(Tb_Ta is
closed)
chapter 12.8.7 "Start Mode Configuration" on
chapter 12.10.5 "Frequency Detection Function" on page
Rexroth Frequency Converter EFC x610
Default
Unit
1
-
0x00000
-
Series
Step
Attri.
-
Stop
-
Run
216.
258.
262.