P01 Group--Start And Stop Control - INVT Goodrive3000 Series Operation Manual

Medium voltage vfd
Hide thumbs Also See for Goodrive3000 Series:
Table of Contents

Advertisement

Goodrive3000 series medium voltage VFD
3: Static autotuning 2
Only the first 3 parameters are autotuned. It is applicable in scenarios where the motor cannot be disconnected from
load.
Note:
1.
Rotary autotuning is recommended.
2.
For 4-quadrant VFDs, it is recommended not to run the rectifier during parameter autotuning, otherwise the accuracy
is affected.
3.
The power difference between the motor and the VFD should be in 2 grades during parameter autotuning, otherwise
affect the accuracy.
Function
code
P00.16
The function code is used to enable the AVR function.
0: Invalid
1: Valid during the whole procedure
The auto-adjusting function of the VFD can eliminate the impact on the output voltage of the VFD because of the bus
voltage fluctuation.
Function
code
Function parameter
P00.18
Note:
1.
After the selected operation is performed, the function code is automatically restored to 0.
2.
Restoring the default values may delete the user password. Exercise caution when using this function.
P01 group––Start and stop control
Function
code
P01.00
0: Direct start. Start from the starting frequency P01.01.
1: Start after DC braking. Start the motor from the starting frequency after DC braking (Set the parameters P01.03 and
P01.04). It is suitable in cases where reverse rotation may occur to the small inertia load during starting.
2. Start after rotating speed tracking. The VFD automatically tracks the rotating speed and direction of the motor, and start
the rotating motor smoothly. It is suitable in cases where reverse rotation may occur to the large inertia load during
starting.
Function
code
Starting frequency of
P01.01
The function code indicates the initial frequency during VFD start. See P01.02 (Starting frequency hold time) for detailed
information.
Name
AVR function
0: Invalid
selection
1: Valid during the whole procedure
Name
0: No operation
1: Restore default values
restore
2: Clear fault records
Name
0: Direct start
Start mode
1: Start after DC braking
2: Start after rotating speed tracking
Name
0.00–50.00Hz
direct start
Description
Description
Description
Description
-64-
Goodrive3000 inverter
Setting range
Default
0–1
1
Setting range
Default
0–2
0
Setting range
Default
0–2
0
Setting range
Default
0.00–50.00
0.50Hz