Goodrive3000 series medium voltage VFD
Function
code
P09.09
PID output upper limit
P09.10
PID output lower limit
The function code is used to set the upper and lower limits of PID regulator output values.
100.0% corresponds to the max. output frequency (P00.03) or max. voltage (P04.31).
Function
code
P09.11
P09.12
Used to set the PID feedback offline detection value. When the feedback value is smaller than or equal to the feedback
offline detection value, and the duration exceeds the value specified by P09.12, the VFD reports "PID feedback offline
fault" and the keypad displays PIDE.
Function
code
PID control
P09.13
Reference
Output
frequency f
Name
P09.10–100.0% (Max. frequency or
voltage)
-100.0%–P09.09 (Max. frequency or
voltage)
Name
Feedback offline
0.0–100.0%
detection value
Feedback offline
0.0–3600.0s
detection time
Output frequency
P09.11
Name
0x0000–0x1111
Ones place:
0: Continue integral control after the frequency
reaches upper/lower limit
1: Stop integral control after the frequency
reaches upper/lower limit
selection
Tens place:
0: Same as the main reference direction
1: Contrary to the main reference direction
Hundreds place:
0: Limit as per the max. frequency
Deviation limit
Feedback
Time t
Time t
Description
Description
t1<T2, so the VFD
continues running
t2=P09.12
PIDE
t1
t2
Running
Fault output PIDE
Description
-110-
Goodrive3000 inverter
Setting range
Default
P09.10–100.0
100.0%
-100.0–P09.09
0.0%
Setting range
Default
0.0–100.0
0.0%
0.0–3600.0
T
Setting range
Default
0x0000–0x1111
0x0001
1.0s