Goodrive3000 series medium voltage VFD
Function
code
P06.15
P06.16
AO1 output upper
P06.17
P06.18
P06.19
AO1 output filter time 0.000–10.000s
P06.20
P06.21
AO2 output upper
P06.22
P06.23
P06.24
AO2 output filter time 0.000–10.000s
The function codes define the relationship between the output value and analog output. When the output value exceeds
the allowed range, the output uses the lower limit or upper limit.
When the analog output is current output, 1mA equals 0.5V.
In different cases, the corresponding analog output of 100% of the output value is different. See each application for
detailed information.
P07 group––Human-machine interface
Function
code
P07.00
When you set the function code to a non-zero number, password protection is enabled.
If you set the function code to 00000, the previous user password is cleared and password protection is disabled.
After the user password is set and takes effect, you cannot enter the parameter menu if you enter an incorrect password.
Name
AO1 output lower
-100.0%–P06.17
limit
AO1 output
corresponding to
-10.00V–10.00V
lower limit
P06.15–100.0%
limit
AO1 output
corresponding to
-10.00V–10.00V
upper limit
AO2 output lower
-100.0%–P06.22
limit
AO2 output
corresponding to
-10.00–10.00V
lower limit
P06.20–100.0%
limit
AO2 output
corresponding to
-10.00V–10.00V
upper limit
-10V
(-20mA )
AO1, AO2
Name
User password
Description
Corresponding
setting
100%
AO
0
10V
(20mA)
-100%
Description
0–65535
-32-
Goodrive3000 rectifier
Setting range
Default
-100.0–P06.17
0.0%
-10.00–10.00
0.00V
P06.15–100.0
100.0%
-10.00–10.00
10.00V
0.000–10.000
0.000s
-100.0–P06.22
0.0%
-10.00–10.00
0.00V
P06.20–100.0
100.0%
-10.00–10.00
10.00V
0.000–10.000
0.000s
Setting range
Default
0–65535
0