Description
Input overvoltage
protection
Input undervoltage
protection
Protection against
input phase loss
Overcurrent
protection
Protection against
overheating
Temperature of
environment
Relative humidity 5%95%
Other
temperature
2.3.2 Goodrive3000 inverter technical specifications
Description
Rated output
current (A)
Power
Rated output
output
voltage (V)
Output power
Control mode
Max. output
frequency
Motor parameter
autotuning
Speed range
Running
control
Speed control
feature
accuracy
Speed fluctuation
Current limit
Speed tracking
When the input voltage is higher than the set overvoltage, report
overvoltage
When the input voltage is lower than the set undervoltage, report
undervoltage
Input phase loss detection
Protection against input overcurrent
IGBT module temperature detection
Standard configuration: LCD and 8 keys, with the copying function;
Keypad
compatible with the LED keypad
-10° C – +50° C. Derating is required when the ambient temperature exceeds
running
40° C.
Storage
-40° C–+70° C
Less than 1000 meters
Altitude
When the VFD installation site altitude exceeds 1000 meters; derate by 1%
for every increase of 100 meters.
Main module: IP00
IP rating
Cabinet of a standard product: IP20, IP54
RS485
Support for MODBUS
Table 2-4 Goodrive3000 inverter technical specifications
See section 2.4.2.
0–Input voltage of rectifier
0.85–0.95 (depend on different motors)
factor
V/F (V/F separation function), open loop vector, closed loop vector
400Hz
Support for static and rotation autotuning
Closed loop vector: 1:1000
Open loop vector: 1:100
Closed loop vector: ± 0.1% of max. speed
Open loop vector: ± 0.5% of max. speed
± 0.3% (open loop vector)
± 0.1% (closed loop vector)
Max. value can be set to 200% of rated current
Used to implement impact-free smooth startup for rotating motors
restart