Goodrive3000 series medium voltage VFD
Function
code
Undervoltage setting
P01.02
value of input voltage
Overvoltage setting
P01.03
value of input voltage
Function
code
P01.06
When P01.06 is set to 0.0s, automatic running is invalid.
When P01.06 is set to a value but not 0.0s: the system will lock phase after power on. The system will operate
automatically if it locks phase and detects successfully.
The automatic running function is valid only when power on. If fault occurs, the function will be invalid automatically and
the system will stop. And after that, the system will be started manually. The function will be enabled if power on again.
Note: Regardless of whether automatic running is valid, the diode rectifier mode is always valid, and the DC bus
is always live.
Function
code
P01.07
Delay of auto fault reset
P01.08
When P01.08 is 0, automatic fault reset is invalid.
When P01.08 is not 0, automatic fault reset is valid and is performed after the time specified by P01.07. Fault reset is
invalid for EF, dIS, PC_T1, OH1, OUT1, OUT2, and OUT3.
Note: A fault is reported when the successive reset count exceeds the count specified by P01.08.
Power on of the
main circuit
Switch on of the
buffer contactor
Bus voltage raises
Main contactor
switch on
P01.01=1
Main contactor switch on?
Buffer contactor
switch off
Ready
Name
Name
Auto-running wait
time
Name
Auto fault reset count
N
Keypad displays tbE
Y
Description
75.0–95.0%
105.0–125.0%
Description
0–3600.0s
Description
0.0–3600.0s
0–10
-24-
Goodrive3000 rectifier
Setting range
Default
75.0–95.0
85.0%
105.0–125.0
115.0%
Setting range
Default
0–3600.0
0.0s
Setting range
Default
0.0–3600.0
1.0s
0–10
0