INVT Goodrive3000 Series Operation Manual page 110

Medium voltage vfd
Hide thumbs Also See for Goodrive3000 Series:
Table of Contents

Advertisement

Goodrive3000 series medium voltage VFD
Function
code
P08.33
FDT2 electrical level
P08.34
P08.35
When the output frequency exceeds the corresponding frequency of FDT electrical level, the multifunction digital output
terminal continuously outputs the signal of "Frequency level detection FDT". The signal is invalid only when the output
frequency decreases to a value lower than the frequency corresponding to (FDT electrical level—FDT lagging detection
value).
Function
code
Detection value for
P08.36
When the output frequency is within the detection range, the multifunction digital output terminal outputs the signal of
"Frequency reached".
Function
code
Enabling dynamic
P08.37
The function code is used to enable dynamic braking.
Note:
1.
After enabling the energy braking, the overvoltage speed loss point automatically raise at 20V.
2.
The parameter is only applicable to the type with built-in braking pipe.
Name
FDT1 lagging
0.0–100.0% (FDT1 electrical level)
detection value
0.00–P00.03 (Max. output frequency)
detection value
FDT2 lagging
0.0–100.0% (FDT2 electrical level)
detection value
FDT level
Y1,
RO1, RO2
Name
frequency being
0.0–P00.03 (Max. output frequency)
reached
Output frequency
Set
frequency
Y,
RO1, RO2
Name
0: Disable
braking
1: Enable
Description
Output frequency f
FDT lag
Time t
Time t
Description
Detection amplitude
Time t
Time t
Description
-104-
Goodrive3000 inverter
Setting range
Default
0.0–100.0
5.0%
0.00–P00.03
50.00Hz
0.0–100.0
5.0%
Setting range
Default
0.0–P00.03
0.00Hz
Setting range
Default
0–1
0

Advertisement