Goodrive3000 series medium voltage VFD
4.3 Operation procedure
You can operate the VFD by using the keypad.
The VFD provides three levels of menus, including:
Function code group number (level-1 menu)
Function code number (level-2 menu)
Function code setting (level-3 menu)
Note: When performing operations on the level-3 menu, you can press the PRG/ESC or DATA/ENT key to return to the
level-2 menu. If you press the DATA/ENT key, the set value of the parameter is saved to the control board first, and then
the level-2 menu is returned, displaying the next function code. If you press the PRG/ESC key, the level-2 menu is
returned directly, without saving the set value of the parameter, and the current function code is displayed.
Basic functions
Level-1 menu
If you enter the level-3 menu but the parameter does not have a digit blinking, the parameter cannot be modified due to
either of the following reasons:
• It is read only. Read-only parameters include actual detection parameters and running record parameters.
• It cannot be modified in running state and can be modified only in stopped state.
4.4 Keypad dimensions
S
P00 group
0
Speed control mode
Figure 4-2 Three-level menu operation flowchart
Figure 4-3 LCD keypad dimension
S
0
P00.00
Level-2 menu
键盘安装开孔图
-20-
S
P00.00
Speed control mode
Present value: 1
1
0: SVC mode 0 (for SM)
1: SVC mode 1 (for AM)
Level-3 menu
HMI