Goodrive3000 series medium voltage VFD
1: AI1
2: AI2
3: AI3
Set the frequency by analog input terminals. The VFD provides 2 channel analog input terminals, among which AI1/AI3 is
the voltage/current option (0–10V/0–20mA) and can be shifted by jumpers while AI2 is the voltage input (-10V–+10V).
Note: When AI1 and AI3 select 0–20mA input, the corresponding voltage of 20mA is 10V.
100.0% of the analog input setting corresponds to Max. output frequency (P00.03) and -100.0% corresponds to the max
output frequency (P00.03).
4: High-speed pulse HDI
Set the frequency by high-speed pulse terminals. The VFD provides 1 channel high-speed pulse input in the range of
0.00–50.00kHz. Pulse frequency range: 0.00–50.00kHz.
100.0% of the high-speed pulse input setting corresponds to Max. output frequency (P00.03) in forward direction and
-100.0% corresponds to max. output frequency (P00.03) in reverse direction.
Note: The pulse setting can be only input by HDI. Set P05.00 (HDI input type selection) to pulse input and P05.51
(HDI pulse input function) to frequency setting input.
5: Simple PLC program
When P00.06 or P00.07 is equal to 5, the VFD runs at simple PLC program mode. Set parameters of P10 group (Simple
PLC and multi-step speed control group) to select corresponding running frequency, running direction, time of acceleration
and deceleration, and duration. Please refer to the description of P10 group functions.
6: Multi-step speed running
When P00.06 or P00.07 is equal to 6, the VFD runs at multi-step speed mode. Set multi-step speed terminals by P05 to
select the current running step and select the current running frequency by parameters of P10.
When P00.06 or P00.07 is not equal to 6, the multi-step speed setting has the priority, but the set step can be only 1–15.
When P00.06 or P00.07 is equal to 6, the set step is 0–15.
7: PID control
When P00.06 or P00.07 is equal to 7, the running mode of the VFD is process PID control. It is necessary to set P09 (PID
control). The running frequency of the VFD is the value after PID effect. As for PID preset source, preset value and
feedback source, refer to the description of P09 PID functions.
8: MODBUS communication
Set the frequency by MODBUS communication. Please see the description of P14 group.
9: PROFIBUS/CANopen communication
Set the frequency by PROFIBUS/ CANopen communication.
Please see the description of P15 group for PROFIBUS communication. PROFIBUS communication card is required.
Please see the description of P15 group for CANopen communication. CANopen communication card is required.
10: Ethernet communication
Set the frequency by Ethernet communication. Please see the description of P16 group. Ethernet communication card is
required.
11: Reserved
Note:
1.
A frequency and B frequency cannot be set to the same frequency reference mode.
2.
The options 3, 4, 9, and 10 are available only when corresponding expansion cards are configured.
-61-