Name
NetRef
State
Voltage Actual

(Vendor Specific Yaskawa Electric (YE) Assy) Speed/Torque Status Input - 151

(0x97)

Input Instance
Word
0
1
151
2
3
Name
Running
During Regenerative Operation
Reset
During Run - Operation Ready
Ready
Alarm
Faulted
oPE
Uv
LOCAL/REMOTE
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual
Voltage command is from network
0: Voltage command is not from network
1: Voltage command is from network
Contains the value from the Control Supervisor (Class 0x29) Instance 1 Attribute 6.
Actual Converter Voltage
Monitors the converter output voltage.
Speed actual data: Output Voltage x 2VS (VS: Voltage scale)
Setting range: 0 - FFFF (Hex.)
For example, when output voltage of 1024 with a voltage scale of 2:
Voltage actual data = 1024 x 2
Byte
Bit 7
Bit 6
0
Faulted
Alarm
1
-
-
2
3
4
5
6
7
Running
0: Stop
1: Running
During Regenerative Operation
0: Converter not in regenerative operation
1: Converter in regenerative operation
Reset
0: -
1: Reset
During Run - Operation Ready
0: Not Ready
1: Ready
Ready
0: Not Ready
1: Ready
Alarm
0: No Alarm
1: Alarm
Faulted
0: No Fault
1: Fault
oPE
0: -
1: oPExx
Undervoltage
0: -
1: Undervoltage
Run command is from network
0: Run command is not from network
11 Input Assemblies (Converter Produces)
Description
2
= 4096 = 1000 (Hex.)
Bit 5
Bit 4
Bit 3
During Run -
Ready
Operation
Reset
Ready
Multi-
Multi-
Multi-
Function
Function
Function
Digital
Digital
Digital
Output 3
Output 2
Output 1
Output Voltage (Low Byte)
Output Voltage (High Byte)
-
-
D1000: Current Actual (Low Byte)
R1000: -
D1000: Current Actual (High Byte)
R1000: -
Description
Bit 2
Bit 1
Bit 0
During
Regenerative
-
Running
Operation
LOCAL/
Uv
oPE
REMOTE
81