0X74) - YASKAWA SI-EN3D Technical Manual

Hide thumbs Also See for SI-EN3D:
Table of Contents

Advertisement

Name
Multi-Function Input 3
Multi-Function Input 4
Multi-Function Input 5
Multi-Function Input 6
Multi-Function Input 7
Multi-Function Input 8
External Fault
Fault Reset
Multi-Function Digital Output 1
Multi-Function Digital Output 2
Multi-Function Digital Output 3
D1000: Voltage Reference
R1000: -
Analog Output 1
Analog Output 2
Digital Outputs
(Vendor Specific Yaskawa Electric (YE) Assy)-High Speed/Torque Control
Output - 116 (0x74)
The first 20 Bytes (0-19) are fixed and the next 20 Bytes can be configured using parameters F7-23 to F7-32. If
an error occurs while trying to write to the dynamic parameters, the appropriate error bit in Assembly 166 will be
set. If more information is needed as to the nature of the error, the extended error status can be read explicitly
through Class 4, Instance 0xA6, Attribute 0x64. This will return 20 Bytes with each dynamic parameter in
Assembly 116 having a Byte dedicated to its extended error status.
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual
Terminal S3 Function Input
0: Terminal S3 Function [H1-03] OFF
1: Terminal S3 Function [H1-03] ON
Terminal S4 Function Input
0: Terminal S4 Function [H1-04] OFF
1: Terminal S4 Function [H1-04] ON
Terminal S5 Function Input
0: Terminal S5 Function [H1-05] OFF
1: Terminal S5 Function [H1-05] ON
Terminal S6 Function Input
0: Terminal S6 Function [H1-06] OFF
1: Terminal S6 Function [H1-06] ON
Terminal S7 Function Input
0: Terminal S7 Function [H1-07] OFF
1: Terminal S7 Function [H1-07] ON
Terminal S8 Function Input
0: Terminal S8 Function [H1-08] OFF
1: Terminal S8 Function [H1-08] ON
External Fault EF0
0: -
1: External Fault [EF0]
Fault Reset
0: -
1: Fault Reset
Terminal M1/M2 (varies by converter model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Terminal M3/M4 (varies by converter model)
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Terminal M5/M6 (varies by converter model)
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different converter series.
D1000: Voltage Reference
Sets converter voltage reference.
R1000: -
MEMOBUS/Modbus (0x0007)
MEMOBUS/Modbus (0x0008)
MEMOBUS/Modbus (0x0009)
Note:
Note: These values are ORed with values in byte 1.
10 Output Assemblies (Converter Consumes)
Description
71