Ethernet/Ip Extended Speed Control Output - 21 (0X15) - YASKAWA SI-EN3D Technical Manual

Hide thumbs Also See for SI-EN3D:
Table of Contents

Advertisement

Name
D1000: Run
R1000: Auto Run
Fault Reset
D1000: Voltage Reference (High Byte)
R1000: -

EtherNet/IP Extended Speed Control Output - 21 (0x15)

Output Instance 
Word
0
21
1
Name
D1000: Run
R1000: Auto Run
D1000: -
R1000: Forced Run
Fault Reset
NetCtrl
D1000: NetRef
R1000: -
D1000: Voltage Reference
R1000: -
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual
D1000: Run converter
0: Stop
1: Run
R1000: Run converter in auto
0: Stop
1: Auto Run
Fault Reset
0: -
1: Fault Reset
D1000: Voltage Reference
Sets converter voltage reference.
Voltage reference data: Voltage reference/2VS (VS: Voltage scale)
Setting range: 0 - FFFF (Hex.)
Example: setting a reference of 4096 with a voltage scale of 2:
Voltage reference data = 4096/2
Unit depends on o1-03.
R1000: -
Byte
Bit 7
Bit 6
D1000:
NetRef
0
-
R1000: -
1
2
3
D1000: Run converter
0: Stop
1: Run
R1000: Run converter in auto
0: Stop
1: Auto Run
D1000: -
R1000: Force run converter
0: Stop
1: Force Run
Fault Reset
0: -
1: Fault Reset
Run command from network
0: Depends on b1-02
1: Run Command is from network
D1000: Voltage command from network
0: Depends on b1-01
1: Voltage command from network
R1000: -
D1000: Voltage Reference
Sets converter voltage reference.
Voltage reference data: Voltage reference/2VS (VS: Voltage scale)
Setting range: 0 - FFFF (Hex.)
Example: setting a reference of 4096 with a voltage scale of 2:
Voltage reference data = 4096/2
Unit depends on o1-03.
R1000: -
10 Output Assemblies (Converter Consumes)
Description
2
= 1024 = 400 (Hex.)
Bit 5
Bit 4
Bit 3
NetCtrl
-
-
-
D1000: Voltage Reference (Low Byte)
R1000: -
D1000: Voltage Reference (High Byte)
R1000: -
Description
2
= 1024 = 400 (Hex.)
Bit 2
Bit 1
Bit 0
D1000: -
D1000: Run
Fault Reset
R1000:
R1000: Auto
Forced Run
Run
67