(Vendor Specific Yaskawa Electric (Ye) Assy) 8 Byte Dynamic 2 Output; (0X75) - YASKAWA SI-EN3D Technical Manual

Hide thumbs Also See for SI-EN3D:
Table of Contents

Advertisement

10 Output Assemblies (Converter Consumes)

(Vendor Specific Yaskawa Electric (YE) Assy) 8 Byte Dynamic 2 Output - 117

(0x75)

Output Instance 
Word
0
117
1
2
3
Name
D1000: Run
R1000: Auto Run
D1000: -
R1000: Forced Run
Multi-Function Input 3
Multi-Function Input 4
Multi-Function Input 5
Multi-Function Input 6
Multi-Function Input 7
Multi-Function Input 8
External Fault
Fault Reset
Multi-Function Digital Output 1
Multi-Function Digital Output 2
74
Byte
Bit 7
Bit 6
Multi-
Multi-
0
Function
Function
Input 8
Input 7
Multi-
Multi-
Function
Function
1
Digital
Digital
Output 3
Output 2
2
3
4 -5
6 -7
D1000: Run converter
0: Stop
1: Run
R1000: Run converter in auto
0: Stop
1: Auto Run
D1000: -
R1000: Force run converter
0: Stop
1: Force Run
Terminal S3 Function Input
0: Terminal S3 Function [H1-03] OFF
1: Terminal S3 Function [H1-03] ON
Terminal S4 Function Input
0: Terminal S4 Function [H1-04] OFF
1: Terminal S4 Function [H1-04] ON
Terminal S5 Function Input
0: Terminal S5 Function [H1-05] OFF
1: Terminal S5 Function [H1-05] ON
Terminal S6 Function Input
0: Terminal S6 Function [H1-06] OFF
1: Terminal S6 Function [H1-06] ON
Terminal S7 Function Input
0: Terminal S7 Function [H1-07] OFF
1: Terminal S7 Function [H1-07] ON
Terminal S8 Function Input
0: Terminal S8 Function [H1-08] OFF
1: Terminal S8 Function [H1-08] ON
External Fault EF0
0: -
1: External Fault [EF0]
Fault Reset
0: -
1: Fault Reset
Terminal M1/M2 (varies by converter model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Terminal M3/M4 (varies by converter model)
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Bit 5
Bit 4
Bit 3
Multi-
Multi-
Multi-
Function
Function
Function
Input 6
Input 5
Input 4
Multi-
Function
-
-
Digital
Output 1
D1000: Voltage Reference (Low Byte)
R1000: -
D1000: Voltage Reference (High Byte)
R1000: -
Programmable Bytes [F7-23], Default: Not Used
Programmable Bytes [F7-24], Default: Not Used
Description
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual
Bit 2
Bit 1
Bit 0
D1000: -
D1000: Run
Multi-
Function
R1000:
R1000: Auto
Input 3
Forced Run
Run
-
Fault Reset
External Fault

Advertisement

Table of Contents
loading

Table of Contents