YASKAWA SI-EN3D Technical Manual page 24

Hide thumbs Also See for SI-EN3D:
Table of Contents

Advertisement

5 Installation Procedure
A - LED Status Ring board
4.
Install the option (A) into the CN5-A connector (C) on the drive and use the included screws (B) to put it in
place.
Tighten the screws to a correct tightening torque:
• 0.5 N∙m to 0.6 N∙m (4.4 in∙lb to 5.3 in∙lb)
Note:
1. A ground wire is not necessary. Do not use the ground wire.
2. Only two screws are necessary to install the option on a GA700 and GA800 drive.
3. Three screws and one ground wire are packaged with option.
A - Option
B - Included screws
5.
Firmly connect the Ethernet communication cable to the option modular connector CN1 port 1 or port 2.
Isolate communication cables from main circuit wiring and other electrical and power lines. Make sure that
you firmly connect the cable end. (Refer to
page 30
for more information.
NOTICE
discharge (ESD) procedures. If you do not follow procedures, it can cause ESD damage to the drive circuitry.
6.
Reattach the LED Status Ring board (E), front cover (C), and keypad (D).
Refer to the drive manuals for more information.
NOTICE
comply could cause erroneous operation.
Note:
• Replace the keypad connector then install the keypad.
• Put the keypad connector tab into the holder when you install the keypad connector to the holder.
24
Figure 5.17 Remove the LED Status Ring Board
Figure 5.18 Install the Option
Damage to Equipment. When you touch the option, make sure that you observe correct electrostatic
Do not pinch cables between the front cover or the LED Status Ring board and the drive. Failure to
B - Temporary placement holes
C - Connector CN5-A
Figure
5.28). Refer to
Communication Cable Specifications on
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual

Advertisement

Table of Contents
loading