15 Web Interface
Procedure: Conditional Email Set-up
1. Click the [Enable] check box to enable the alert.
2. Define the condition that will trigger the email by selecting a monitor parameter, a comparator, and a value.
Set the conditions to send alerts from the [Condition] drop-down selection. If choosing only one condition and
no OR or AND are needed, set the [OR/AND] drop-down selection to [—].
3. Enter the email address where the alert will be sent.
4. Enter the message that will appear in the email contents.
5. Enter the email subject.

Parameter Access Page

The Parameter Access page allows the user to read and write parameters from the drive. Write access is restricted
until a valid password is entered.
The MEMOBUS/Modbus address for the drive parameter being accessed must be entered in hexadecimal.
Clicking [Read] will load and display the current value of the given MEMOBUS/Modbus Address.
Clicking [Set] will save the given value to the given MEMOBUS/Modbus address.
After a [Read] or [Set] command is given, Status will display [Waiting] while the action is being carried out, then
[Read Successful] or [Write Successful] is displayed when finished.
116
Figure 15.6 Email Alerts Page View
Figure 15.7 Parameter Access Page View
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual