YASKAWA SI-EN3D Technical Manual page 34

Hide thumbs Also See for SI-EN3D:
Table of Contents

Advertisement

6 Related Drive Parameters
No.
Name
(Hex.)
F7-06
Subnet Mask 2
(03EA)
F7-07
Subnet Mask 3
(03EB)
F7-08
Subnet Mask 4
(03EC)
F7-09
Gateway Address 1
(03ED)
F7-10
Gateway Address 2
(03EE)
F7-11
Gateway Address 3
(03EF)
F7-12
Gateway Address 4
(03F0)
F7-13
Address Startup Mode
(03F1)
F7-14
Duplex Mode Selection
(03F2)
34
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Subnet Mask. Sets the second most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Subnet Mask. Sets the third most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Subnet Mask. Parameter F7-08 sets the fourth most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Gateway address. Sets the most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Gateway address. Sets the second most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Gateway address. Sets the third most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Sets the static/fixed Gateway address. Parameter F7-12 sets the fourth most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Selects how the option address is set.
0 : Static (Use F7-01 to F7-12 to set.)
1 : BOOTP (Use network address.)
2 : DHCP (Use network address.)
Note:
You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set F6-15 = 1 [Comm. Option Parameters Reload = Reload Now].
Selects duplex mode setting (Port 1/Port 2).
0 : Half/Half
1 : Auto/Auto
2 : Full/Full
3 : Half/Auto
4 : Half/Full
5 : Auto/Half
6 : Auto/Full
7 : Full/Half
8 : Full/Auto
Note:
• When you set this parameter to 0, 2, 3, 4, 7, or 8, you must also set F7-15 = 0.0.
• This option sets the duplex mode for port 1 and port 2 as specified by these F7-14.
–When 0: Half/Half, port 1/port 2 is set to Half.
–When 1: Auto/Auto, port 1/port 2 is set to Auto.
–When 2: Full/Full, port 1/port 2 is set to Full.
–When 3: Half/Auto, port 1 is set to Half and port 2 is set to Auto.
–When 4: Half/Full, port 1 is set to Half and port 2 is set to Full.
–When 5: Auto/Half, port 1 is set to Auto and port 2 is set to Half.
–When 6: Auto/Full, port 1 is set to Auto and port 2 is set to Full.
–When 7: Full/Half, port 1 is set to Full and port 2 is set to Half.
Description
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual
Default
(Range)
255
(0 - 255)
255
(0 - 255)
0
(0 - 255)
192
(0 - 255)
168
(0 - 255)
1
(0 - 255)
1
(0 - 255)
2
(0 - 2)
1
(0 - 8)

Advertisement

Table of Contents
loading

Table of Contents