(Vendor Specific Yaskawa Electric (Ye) Assy) 24-Byte Dynamic Input - 170 (0Xaa) - YASKAWA SI-EN3D Technical Manual

Hide thumbs Also See for SI-EN3D:
Table of Contents

Advertisement

Name
Output Frequency
Dynamic Inputs
(Vendor Specific Yaskawa Electric (YE) Assy) 24-Byte Dynamic Input - 170
(0xAA)
Input Instance
Word
0
1
2
3
170
4
5
6
7
8
9
10
11
Name
Running
ZSP
REV Running
Fault Reset
Speed Agree
Ready
Alarm
Faulted
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Actual Drive Speed
Monitors drive output frequency.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Contains the data to be read from the MEMOBUS/Modbus address defined in the given parameter. A value of 0 in the given
parameter means it will return the default data as defined in the table above.
Byte
Bit 7
Bit 6
0
Faulted
Alarm
1
ZSV
-
2
3
4 - 5
6 - 7
8 - 9
10 - 11
12 - 13
14 - 15
16 - 17
18 - 19
20 - 21
22 - 23
Running
0: Stop
1: Forward or Reverse Running
Zero Speed
0: Running
1: Stop or DC Injection Braking
Reverse Running
0: Not Reverse Running
1: Reverse Running
Fault Reset
0: -
1: Fault Reset
Speed Agree
0: -
1: Speed actual at speed reference
Ready
0: Not Ready
1: Ready
Alarm
0: No Alarm
1: Alarm
Faulted
0: No Fault
1: Fault
9 Input Assemblies (Drive Produces)
Description
Bit 5
Bit 4
Bit 3
Ready
Speed Agree
Fault Reset
Multi-
Multi-
Multi-
Function
Function
Function
Digital
Digital
Digital
Output 3
Output 2
Output 1
Output Frequency (Low Byte)
Output Frequency (High Byte)
Dynamic Input 1 [F7-33], Default: Fault Code
Dynamic Input 2 [F7-34], Default: Output Power [U1-08]
Dynamic Input 3 [F7-35], Default: Analog Input 2
Dynamic Input 4 [F7-36], Default: Digital Input
Dynamic Input 5 [F7-37], Default: Analog Input 3
Dynamic Input 6 [F7-38], Default: PG 2 Counter
Dynamic Input 7 [F7-39], Default: Net Ref and Net Ctrl
Dynamic Input 8 [F7-40], Default: Drive Software Version
Dynamic Input 9 [F7-41], Default: Not Used
Dynamic Input 10 [F7-42], Default: Not Used
Description
Bit 2
Bit 1
Bit 0
REV Running
ZSP
Running
LOCAL/
Uv
oPE
REMOTE
65

Advertisement

Table of Contents
loading

Table of Contents