(Vendor Specific Yaskawa Electric (Ye) Assy) 12-Byte Dynamic Input; (0Xa8) - YASKAWA SI-EN3D Technical Manual

Hide thumbs Also See for SI-EN3D:
Table of Contents

Advertisement

11 Input Assemblies (Converter Produces)
Name
Running
During Regenerative Operation
Reset
During Run - Operation Ready
Ready
Alarm
Faulted
oPE
Uv
LOCAL/REMOTE
Multi-Function Digital Output 1
Multi-Function Digital Output 2
Multi-Function Digital Output 3
Output Voltage
F7-33 Alarm Code
D1000: F7-34 Output Power
R1000: F7-34 Not Used

(Vendor Specific Yaskawa Electric (YE) Assy) 12-Byte Dynamic Input 4 - 168

(0xA8)

Input Instance
Word
168
0
88
Running
0: Stop
1: Running
During Regenerative Operation
0: Converter not in regenerative operation
1: Converter in regenerative operation
Reset
0: -
1: Reset
During Run - Operation Ready
0: Not Ready
1: Ready
Ready
0: Not Ready
1: Ready
Alarm
0: No Alarm
1: Alarm
Faulted
0: No Fault
1: Fault
oPE
0: -
1: oPExx
Undervoltage
0: -
1: Undervoltage
Run command is from network
0: Run command is not from network
1: Run command is from network
Terminal M1/M2 (varies by converter model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Terminal M3/M4 (varies by converter model)
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Terminal M5/M6 (varies by converter model)
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Converter Output Voltage
Programmable: MEMOBUS/Modbus (0x7F)
D1000: Programmable: MEMOBUS/Modbus (0x47)
Monitor parameter U1-08
R1000: -
Byte
Bit 7
Bit 6
0
Faulted
Alarm
1
-
-
Description
Bit 5
Bit 4
Bit 3
During Run -
Ready
Operation
Reset
Ready
Multi-
Multi-
Multi-
Function
Function
Function
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual
Bit 2
Bit 1
Bit 0
During
Regenerative
-
Running
Operation
LOCAL/
Uv
oPE
REMOTE

Advertisement

Table of Contents
loading

Table of Contents