YASKAWA SI-EN3D Technical Manual page 83

Hide thumbs Also See for SI-EN3D:
Table of Contents

Advertisement

Input Instance
Word
10
11
12
13
14
15
16 - 19
Name
Running
During Regenerative Operation
Reset
During Run - Operation Ready
Ready
Alarm
Faulted
oPE
Uv
LOCAL/REMOTE
Multi-Function Digital Output 1
Multi-Function Digital Output 2
Multi-Function Digital Output 3
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual
Byte
Bit 7
Bit 6
19
20
21
22
23
24
25
26
27
28
29
30
31
32 - 39
Running
0: Stop
1: Running
During Regenerative Operation
0: Converter not in regenerative operation
1: Converter in regenerative operation
Reset
0: -
1: Reset
0: Not Ready
1: Ready
Ready
0: Not Ready
1: Ready
Alarm
0: No Alarm
1: Alarm
Faulted
0: No Fault
1: Fault
oPE
0: -
1: oPExx
Undervoltage
0: -
1: Undervoltage
Run command is from network
0: Run command is not from network
1: Run command is from network
Terminal M1/M2 (varies by converter model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Terminal M3/M4 (varies by converter model)
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Note:
The names of the digital outputs are different for different converter series.
Terminal M5/M6 (varies by converter model)
11 Input Assemblies (Converter Produces)
Bit 5
Bit 4
Bit 3
Error Code (High Byte)
Alarm Code 2 (Low Byte)
Alarm Code 2 (High Byte)
Alarm Code 3 (Low Byte)
Alarm Code 3 (High Byte)
Terminal A3 Input (Low Byte)
Terminal A3 Input (High Byte)
Digital Input (Low Byte)
Digital Input (High Byte)
Terminal A1 Input (Low Byte)
Terminal A1 Input (High Byte)
-
-
Reserved
Description
Bit 2
Bit 1
Bit 0
83