Name
Multi-Function Digital Output 3
Speed Reference
Dynamic Outputs
(Vendor Specific Yaskawa Electric (YE) Assy) 12 Byte Dynamic Output - 118
(0x76)
Output Instance
Word
0
118
1
2
3
4
5
Name
Run Fwd
Run Rev
Multi-Function Input 3
Multi-Function Input 4
Multi-Function Input 5
Multi-Function Input 6
Multi-Function Input 7
Multi-Function Input 8
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Terminal M5/M6 (varies by drive model)
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Speed Command
Sets drive speed reference.
-1
Unit is min
or determined by o1-03.
Unit is not affected by Speed Scale SS.
Contains the data to be written to the MEMOBUS/Modbus address defined in the given parameter. A value of 0 in the given
parameter means it is not used, therefore the value received for this given parameter will not be written to any MEMOBUS/
Modbus register. If the PPA is Input Assembly 166, then any errors occurring during a write will be flagged. Refer to page
58
for more information.
Byte
Bit 7
Bit 6
Multi-
Multi-
0
Function
Function
Input 8
Input 7
Multi-
Multi-
Function
Function
1
Digital
Digital
Output 3
Output 2
2
3
4 - 5
6 - 7
8 - 9
10 - 11
Forward Run Command
0: Stop
1: Forward Run
Reverse Run Command
0: Stop
1: Reverse Run
Terminal S3 Function Input
0: Terminal S3 Function [H1-03] OFF
1: Terminal S3 Function [H1-03] ON
Terminal S4 Function Input
0: Terminal S4 Function [H1-04] OFF
1: Terminal S4 Function [H1-04] ON
Terminal S5 Function Input
0: Terminal S5 Function [H1-05] OFF
1: Terminal S5 Function [H1-05] ON
Terminal S6 Function Input
0: Terminal S6 Function [H1-06] OFF
1: Terminal S6 Function [H1-06] ON
Terminal S7 Function Input
0: Terminal S7 Function [H1-07] OFF
1: Terminal S7 Function [H1-07] ON
Terminal S8 Function Input
0: Terminal S8 Function [H1-08] OFF
1: Terminal S8 Function [H1-08] ON
8 Output Assemblies (Drive Consumes)
Description
Bit 5
Bit 4
Bit 3
Multi-
Multi-
Multi-
Function
Function
Function
Input 6
Input 5
Input 4
Multi-
Function
-
-
Digital
Output 1
Speed Reference (Low Byte)
Speed Reference (High Byte)
Dynamic Output 1 [F7-23], Default: Not Used
Dynamic Output 2 [F7-24], Default: Not Used
Dynamic Output 3 [F7-25], Default: Not Used
Dynamic Output 4 [F7-26], Default: Not Used
Description
Bit 2
Bit 1
Bit 0
Multi-
Function
Run Rev
Run Fwd
Input 3
-
Fault Reset
External Fault
47