7 PROFINET Messaging

Yaskawa Vendor-Specific Control and Status Words

The Control Word and the Status Word

The contents of the Control Word and the Status Word are detailed in

Frequency Reference

Frequency Reference is a 16-bit word containing the desired output frequency.

Output Frequency

Output Frequency is a 16-bit word containing the current output frequency of the drive.
Table 7.3 Yaskawa-Specific Control Word and Status Word
Yaskawa-Specific Control Word
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
*1
Bit 11 is not used for GA500.
54
Description
Run bit
Reverse run bit
EF0
Fault Reset
DI1
DI2
DI3
DI4
DI5
DI6
DI7
*1
DI8
Not Used
Not Used
Not Used
Not Used
YASKAWA TOEP C730600 89B PROFINET Installation Manual
Table
Yaskawa-Specific Status Word
Bit
Description
0
1
Zero Speed
2
Reverse Operation
3
Reset Signal Input Active
4
5
6
7
8
9
10
11
12
13
14
Net Reference
15
Net Control
7.3.
Running
At Speed
Ready
Alarm
Fault
oPE Fault
Uv Return
2nd Motor
ZSV
Not Used
Not Used