(Vendor Specific Yaskawa Electric (Ye) Assy) 24 Byte Dynamic Output; (0X78) - YASKAWA SI-EN3D Technical Manual

Hide thumbs Also See for SI-EN3D:
Table of Contents

Advertisement

Name
Multi-Function Input 4
Multi-Function Input 5
Multi-Function Input 6
Multi-Function Input 7
Multi-Function Input 8
External Fault
Fault Reset
Multi-Function Digital Output 1
Multi-Function Digital Output 2
Multi-Function Digital Output 3
Speed Reference
Dynamic Outputs

(Vendor Specific Yaskawa Electric (YE) Assy) 24 Byte Dynamic Output - 120

(0x78)

Output Instance
Word
0
120
1
2
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual
0: Terminal S3 Function [H1-03] OFF
1: Terminal S3 Function [H1-03] ON
Terminal S4 Function Input
0: Terminal S4 Function [H1-04] OFF
1: Terminal S4 Function [H1-04] ON
Terminal S5 Function Input
0: Terminal S5 Function [H1-05] OFF
1: Terminal S5 Function [H1-05] ON
Terminal S6 Function Input
0: Terminal S6 Function [H1-06] OFF
1: Terminal S6 Function [H1-06] ON
Terminal S7 Function Input
0: Terminal S7 Function [H1-07] OFF
1: Terminal S7 Function [H1-07] ON
Terminal S8 Function Input
0: Terminal S8 Function [H1-08] OFF
1: Terminal S8 Function [H1-08] ON
External Fault EF0
0: -
1: External Fault [EF0]
Fault Reset
0: -
1: Fault Reset
Terminal M1/M2 (varies by drive model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Terminal M3/M4 (varies by drive model)
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Terminal M5/M6 (varies by drive model)
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Speed Command
Sets drive speed reference.
-1
Unit is min
or determined by o1-03.
Unit is not affected by Speed Scale SS.
Contains the data to be written to the MEMOBUS/Modbus address defined in the given parameter. A value of 0 in the given
parameter means it is not used, therefore the value received for this given parameter will not be written to any MEMOBUS/
Modbus register. If the PPA is Input Assembly 166, then any errors occurring during a write will be flagged. Refer to page
58
for more information.
Byte
Bit 7
Bit 6
Multi-
Multi-
0
Function
Function
Input 8
Input 7
Multi-
Multi-
Function
Function
1
Digital
Digital
Output 3
Output 2
2
3
4 - 5
8 Output Assemblies (Drive Consumes)
Description
Bit 5
Bit 4
Bit 3
Multi-
Multi-
Multi-
Function
Function
Function
Input 6
Input 5
Input 4
Multi-
Function
-
-
Digital
Output 1
Speed Reference (Low Byte)
Speed Reference (High Byte)
Dynamic Output 1 [F7-23], Default: Not Used
Bit 2
Bit 1
Bit 0
Multi-
Function
Run Rev
Run Fwd
Input 3
-
Fault Reset
External Fault
49