9 Input Assemblies (Drive Produces)
Name
Speed Agree
Ready
Alarm
Faulted
oPE
Uv
LOCAL/REMOTE
Multi-Function Digital Output 1
Multi-Function Digital Output 2
Multi-Function Digital Output 3
Output Frequency
Dynamic Inputs
(Vendor Specific Yaskawa Electric (YE) Assy) 12-Byte Dynamic Input - 168
(0xA8)
Input Instance
Word
0
1
168
2
3
4
5
62
Speed Agree
0: -
1: Speed actual at speed reference
Ready
0: Not Ready
1: Ready
Alarm
0: No Alarm
1: Alarm
Faulted
0: No Fault
1: Fault
oPE
0: -
1: oPExx
Undervoltage
0: -
1: Undervoltage
Run command is from network
0: Run command is not from network
1: Run command is from network
Terminal M1/M2 (varies by drive model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Terminal M3/M4 (varies by drive model)
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Terminal M5/M6 (varies by drive model)
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Actual Drive Speed
Monitors drive output frequency.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Contains the data to be read from the MEMOBUS/Modbus address defined in the given parameter. A value of 0 in the given
parameter means it will return the default data as defined in the table above.
Byte
Bit 7
Bit 6
0
Faulted
Alarm
1
ZSV
-
2
3
4 - 5
6 - 7
8 - 9
10 - 11
Description
Bit 5
Bit 4
Bit 3
Ready
Speed Agree
Fault Reset
Multi-
Multi-
Multi-
Function
Function
Function
Digital
Digital
Digital
Output 3
Output 2
Output 1
Output Frequency (Low Byte)
Output Frequency (High Byte)
Dynamic Input 1 [F7-33], Default: Alarm Code
Dynamic Input 2 [F7-34], Default: Output Power [U1-08]
Dynamic Input 3 [F7-35], Default: Analog Input 2
Dynamic Input 4 [F7-36], Default: Digital Input
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual
Bit 2
Bit 1
Bit 0
REV Running
ZSP
Running
LOCAL/
Uv
oPE
REMOTE