(Vendor Specific Yaskawa Electric (Ye) Assy) 18 Byte Dynamic 7 Output; (0X77) - YASKAWA SI-EN3D Technical Manual

Hide thumbs Also See for SI-EN3D:
Table of Contents

Advertisement

10 Output Assemblies (Converter Consumes)
Name
External Fault
Fault Reset
Multi-Function Digital Output 1
Multi-Function Digital Output 2
Multi-Function Digital Output 3
D1000: Voltage Reference
R1000: -
Programmable Bytes

(Vendor Specific Yaskawa Electric (YE) Assy) 18 Byte Dynamic 7 Output - 119

(0x77)

Output Instance 
Word
0
1
119
2
3
4
5
6
7
8
Name
D1000: Run
R1000: Auto Run
D1000: -
R1000: Forced Run
76
0: Terminal S8 Function [H1-08] OFF
1: Terminal S8 Function [H1-08] ON
External Fault EF0
0: -
1: External Fault [EF0]
Fault Reset
0: -
1: Fault Reset
Terminal M1/M2 (varies by converter model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Terminals M3 and M4
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Terminals M5 and M6
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
D1000: Voltage Reference
Sets converter voltage reference.
R1000: -
Contains the data to be written to the MEMOBUS/Modbus address defined in the given parameter.
A value of 0 in the given parameter means it is not used, therefore the value received for this given parameter will not be
written to any MEMOBUS/Modbus register.
Byte
Bit 7
Bit 6
Multi-
Multi-
0
Function
Function
Input 8
Input 7
Multi-
Multi-
Function
Function
1
Digital
Digital
Output 3
Output 2
2
3
4 -5
6 -7
8 -9
10 -11
12 -13
14 -15
16 -17
D1000: Run converter
0: Stop
1: Run
R1000: Run converter in auto
0: Stop
1: Auto Run
D1000: -
R1000: Force run converter
0: Stop
1: Force Run
Description
Bit 5
Bit 4
Bit 3
Multi-
Multi-
Multi-
Function
Function
Function
Input 6
Input 5
Input 4
Multi-
Function
-
-
Digital
Output 1
D1000: Voltage Reference (Low Byte)
R1000: -
D1000: Voltage Reference (High Byte)
R1000: -
Programmable Bytes [F7-23], Default: Not Used
Programmable Bytes [F7-24], Default: Not Used
Programmable Bytes [F7-25], Default: Not Used
Programmable Bytes [F7-26], Default: Not Used
Programmable Bytes [F7-27], Default: Not Used
Programmable Bytes [F7-28], Default: Not Used
Programmable Bytes [F7-29], Default: Not Used
Description
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual
Bit 2
Bit 1
Bit 0
D1000: -
D1000: Run
Multi-
Function
R1000:
R1000: Auto
Input 3
Forced Run
Run
-
Fault Reset
External Fault