5 Installation Procedure
A - Drive grounding terminal (FE)
B - Option
C - Included screws
D - Ground screw
E - Drive front cover
F - Keypad
Install the Option
Use this procedure to install the option.
DANGER
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before
servicing, disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal
capacitor stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage
decreases below 50 Vdc. When all indicators are OFF, measure for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock.
1.
Remove the keypad (B) and front cover (A).
Shut off power to the drive and wait for the time specified on the drive warning label at a minimum. Make
sure that the charge indicator LED is unlit, then remove the keypad and front cover. Refer to the drive
manuals for more information.
NOTICE
discharge (ESD) procedures. If you do not follow procedures, it can cause ESD damage to the drive circuitry.
26
Figure 5.20 Drive Components with Option
Damage to Equipment. When you touch the option, make sure that you observe correct electrostatic
G - LED label
H - Ground wire
I - Option modular connector CN1 port 1 (RJ45)
J - Option modular connector CN1 port 2 (RJ45)
K - Insertion point for connector (HV600: CN5,
FP605: CN5-A)
L - Connector (HV600: CN5, FP605: CN5-A)
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual