Name
Multi-Function Input 3
Multi-Function Input 4
Multi-Function Input 5
Multi-Function Input 6
Multi-Function Input 7
Multi-Function Input 8
External Fault
Fault Reset
Multi-Function Digital Output 1
Multi-Function Digital Output 2
Multi-Function Digital Output 3
Speed Reference
Torque Reference/Torque Limit
Torque Compensation
Analog Output 1
Analog Output 2
Digital Outputs
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual
0: Stop
1: Reverse Run
Terminal S3 Function Input
0: Terminal S3 Function [H1-03] OFF
1: Terminal S3 Function [H1-03] ON
Terminal S4 Function Input
0: Terminal S4 Function [H1-04] OFF
1: Terminal S4 Function [H1-04] ON
Terminal S5 Function Input
0: Terminal S5 Function [H1-05] OFF
1: Terminal S5 Function [H1-05] ON
Terminal S6 Function Input
0: Terminal S6 Function [H1-06] OFF
1: Terminal S6 Function [H1-06] ON
Terminal S7 Function Input
0: Terminal S7 Function [H1-07] OFF
1: Terminal S7 Function [H1-07] ON
Terminal S8 Function Input
0: Terminal S8 Function [H1-08] OFF
1: Terminal S8 Function [H1-08] ON
External Fault EF0
0: -
1: External Fault [EF0]
Fault Reset
0: -
1: Fault Reset
Terminal M1/M2 (varies by drive model)
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Terminal M3/M4 (varies by drive model)
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Terminal M5/M6 (varies by drive model)
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Speed Command
Sets drive speed reference.
Unit is min
-1
or determined by o1-03.
Torque Reference/Torque Limit
Sets the Torque Reference/Torque Limit. Sets in units of 0.1%.
Sets the Torque Reference when using Torque Control [d5-01 = 1].
Sets the Torque Limit when using Speed Control [d5-01 = 0].
The Torque Reference/Torque Limit are disabled when F6-06 = 0.
Torque Compensation
Sets the amount of Torque Compensation
Sets in units of 0.1%.
MEMOBUS/Modbus (0x0007)
MEMOBUS/Modbus (0x0008)
MEMOBUS/Modbus (0x0009)
Note:
These values are ORed with values in byte 1.
8 Output Assemblies (Drive Consumes)
Description