Input Assemblies (Converter Produces); Ethernet/Ip Basic Speed Control Input - 70 (0X46); Ethernet/Ip Extended Speed Control Input - 71 (0X47) - YASKAWA SI-EN3D Technical Manual

Hide thumbs Also See for SI-EN3D:
Table of Contents

Advertisement

Name
D1000: Voltage Reference
R1000: -
Programmable Bytes
11

Input Assemblies (Converter Produces)

Note:
The convention in this manual is from the PLC perspective. An "Input Assembly" is outputted from this node and read by the PLC. This
section details "Input Assemblies" that are "Produced" by the converter.

EtherNet/IP Basic Speed Control Input - 70 (0x46)

Input Instance
Word
0
70
1
Name
Running
Faulted
Voltage Actual

EtherNet/IP Extended Speed Control Input - 71 (0x47)

Input Instance
Word
0
71
1
Name
Faulted
Alarm
Running
During Regenerative Operation
Ready
YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different converter series.
D1000: Voltage Reference
Sets converter voltage reference.
R1000: -
Contains the data to be written to the MEMOBUS/Modbus address defined in the given parameter.
A value of 0 in the given parameter means it is not used, therefore the value received for this given parameter will not be
written to any MEMOBUS/Modbus register.
Byte
Bit 7
Bit 6
0
-
-
1
2
3
Running
Faulted
0: No Fault
1: Fault
Actual Converter Voltage
Monitors the converter output voltage.
Voltage actual data: Output Voltage x 2VS (VS: Voltage scale)
Setting range: 0 - FFFF (Hex.)
For example, when output voltage of 1024 with a voltage scale of 2:
Voltage actual data = 1024×2
Byte
Bit 7
Bit 6
0
-
NetRef
1
2
3
Faulted
0: No Fault
1: Fault
Alarm
0: No Alarm
1: Alarm
Running
Converter in regenerative operation
Ready
0: Not Ready
1: Ready
11 Input Assemblies (Converter Produces)
Description
Bit 5
Bit 4
Bit 3
-
-
-
Voltage Actual (Low Byte)
Voltage Actual (High Byte)
Description
2
= 4096 = 1000 (Hex.)
Bit 5
Bit 4
Bit 3
During
NetCtrl
Ready
Regenerative
Operation
State
Voltage Actual (Low Byte)
Voltage Actual (High Byte)
Description
Bit 2
Bit 1
-
Faulted
-
Bit 2
Bit 1
Running
Alarm
Bit 0
Running
Bit 0
Faulted
79