Dynamic Output Assembly (Vendor Specific Yaskawa Electric (Ye) Assy); (0X6D) - YASKAWA SI-N3 Technical Manual

Hide thumbs Also See for SI-N3:
Table of Contents

Advertisement

Name
Multi-Function Input 8
External Fault
Fault Reset
Function Code
1000-Series, GA500: Multi-Function Digital
Output
GA700, GA800, FP605: Multi-Function Digital
Output 1
1000-Series, GA500: Multi-Function Photocoupler
1
GA700, GA800, FP605: Multi-Function Digital
Output 2
1000-Series, GA500: Multi-Function Photocoupler
2
GA700, GA800, FP605: Multi-Function Digital
Output 3
*2
Multi-Function Digital Output 4
Torque Reference/Torque Limit
Register Number
Register Data
*1
Terminals are different for different drive models. Refer to
for more information.
*2
Multi-function digital output 4 is not available for 1000-Series, GA500, GA800, or FP605 drives.
*3
Register numbers 0x0001 and 0x0009 are disabled.
Note:
1. This is a paired assembly (108/158).
2. Refer to the MEMOBUS/Modbus Data Table in the drive Technical Manual for a list of monitor data using the MEMOBUS/Modbus
message area.

Dynamic Output Assembly (Vendor Specific Yaskawa Electric (YE) Assy) - 109

(0x6D)

This is a dynamic assembly. You can set the parameters that are used.
Note:
The drive is compatible with option software versions 1111 and later.
YASKAWA SIEP C730600 84F DeviceNet Technical Manual
1: Terminal S7 Function [H1-07] ON
Terminal S8 Function Input
0: Terminal S8 Function [H1-08] OFF
1: Terminal S8 Function [H1-08] ON
External Fault EF0
0: -
1: External Fault [EF0]
Fault Reset
0: -
1: Fault Reset
MEMOBUS/Modbus Function Code
Refer to
Table 8.4
for information.
1000-Series, GA700, GA800, FP605: Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
GA500: Terminal MA/MB
0: MA/MB OFF
1: MA/MB ON
This function is enabled only when H2-01 = F.
*1
1000-Series, GA500: Terminal P1
0: P1 OFF
1: P1 ON
GA700, GA800, FP605: Terminal M3/M4
0: M3/M4 OFF
1: M3/M4 ON
This function is enabled only when H2-02 = F.
*1
1000-Series, GA500: Terminal P2
0: P2 OFF
1: P2 ON
*1
GA700, GA800: Terminal P1
0: P1 OFF
1: P1 ON
FP605
0: MD/MF OFF
1: MD/MF ON
This function is enabled only when H2-03 = F.
*1
Terminal P2
0: P2 OFF
1: P2 ON
This function is enabled only when H2-04 = F.
Torque Reference/Torque Limit
Sets the Torque Reference/Torque Limit. Sets in units of 0.1%.
Sets the Torque Reference when using d5-01 = 1 [Torque Control Selection = Torque Control].
Sets the Torque Limit when using d5-01 = 0 [Torque Control Selection = Speed Control].
The Torque Reference/Torque Limit are disabled when F6-06 = 0 [Torque Reference/Limit by Comm = Disabled].
MEMOBUS/Modbus Register Number
MEMOBUS/Modbus Register Data
Terminals that Change depending on the Model of the Drive on page 55
8 Output Assemblies (Drive Consumes)
Description
*3
47