Figure 9: Abort Active Profile; Figure 10: Setpoint Change - Jamesway Sentry Manual

Display panel
Table of Contents

Advertisement

If the selected machine is
currently executing a profile,
the operator will be asked if
they would like to cancel the
profile mode, or leave it
unchanged and abort this
function. To cancel the profile
and continue to change the
setpoints, move the cursor
down to 'Change Setpoints'
and press "ENTER".
The profile is not actually
aborted until new setpoints are
sent to the machine, thus it is
still possible to abort this
function after this step and
leave the profile mode unchanged.
The screen at right displays the
current setpoints and allows
the operator to change the
targets. To change setpoints,
move the cursor to the desired
field using the "UP" and
"DOWN" arrow keys and type
in the new numeric value.
Pressing "EXIT" while typing
in a number changes the field
back to the previous value.
The values must be entered in
the units indicated in
parentheses. The units can be
changed using functions under
the 'Display' menu. Valid
entry values are 70.0 to 101°F
(21.1 to 38.3°C) for temperature, and 30.0 to 90.0% RH for relative humidity. Wet bulb values are
converted to RH and must fall within the humidity range listed above. Once all values are entered
correctly, press "ENTER" to continue, or "EXIT" to abort. If the screen is aborted, the setpoints will
remain unchanged.

Figure 9: Abort Active Profile

Figure 10: Setpoint Change

Sentry Control System 13