Figure 202: Pta410 Machine Controller Switch Settings For Jm Machines - Jamesway Sentry Manual

Display panel
Table of Contents

Advertisement

The PTA410 may have either one
of the two switches illustrated above.
This illustration shows a switch in the
"on" or "closed" position.
SW1-4 along with SW2
designate the unit type
Room Number
1234
Open
SW1

Figure 202: PTA410 Machine Controller Switch Settings for JM Machines

120 Sentry Control System
Room #8
Room #7
Room #6
Room #5
Room #4
JM Incubator
Room #3
1234
Room #2
Room #1
JM Hatcher
Unit Type
1234
Open
SW2
Set option switches
6,7,8 to closed/on
for incubators
4 Trolley
Option
switches
1 and 2
5 Trolly
designate
machine
width
6 Trolly
1 Section
Option
switches
3 and 4
2 Section
designate
number of
sections
3 Section
Not connected
Option
switch 5
designates
Connected
damper
Fan reverses
Water cooling on at 0.4˚C
Blower on at 0.2˚C
Hatcher options
Blower on at 0.4˚C
Water cooling on at 0.2˚C
Fan does not referse
12345678
Options
Open
SW3