Determining The Faulty Area And Alarm Severity - Huawei FusionModule2000-S User Manual

Smart modular data center
Hide thumbs Also See for FusionModule2000-S:
Table of Contents

Advertisement

FusionModule2000-S Smart Modular Data Center
User Manual
Procedure
Step 1 Log in to the ECC800-Pro WebUI.
Step 2 Click Active Alarms on the home page to view the current alarm information.
Step 3 Collect alarm information.
----End
Example
Table 6-12 Alarm information collection table
Alar
m
SN

6.2.3 Determining the Faulty Area and Alarm Severity

After receiving a fault alarm, determine the alarm severity immediately. If the
alarm is critical, perform emergency operations. If not, handle it as a common
alarm.
Issue 03 (2021-07-15)
NO TE
After an alarm is generated, immediately collect the following information:
● Occurrence time and place
● Detailed fault symptoms
● Operations performed before the fault occurs
● Services and scope affected by the fault alarm
● Measures taken after the fault occurs and the effect
Alar
Alar
Alarm
m
m
Locatio
Na
Gene
n
me
ratio
n
Time
-
-
-
-
-
-
NO TE
Critical alarms include the following:
● Alarms that cause system shutdown
● Alarms that result in equipment damage or affect equipment usage
● Alarms that may result in serious results (such as fire or communication interruption)
Copyright © Huawei Technologies Co., Ltd.
Descrip
Alarm
tion
Type
-
-
-
-
-
-
6 Operation and Maintenance
Curren
Impact
t
Operat
ion
-
-
-
-
-
-
Measur
es
Taken
and
Effect
-
-
-
238