Procedure
Step 1 (Optional) Check whether the cabinet door lock is leveled to 2000 (+3) mm. If
not, adjust it.
Step 2 (Optional) If the cabinet door still cannot be opened after Step 1 is performed,
adjust the position of the cabinet electronic clasp lock by using the slotted holes
until the cabinet door can be opened and closed properly.
Step 3 Set device addresses for cabinet electronic clasp locks.
Figure 5-22 DIP switch addresses of the cabinet electronic locks
● The number indicates the DIP switch setting of the electronic clasp lock.
● The RS485_R DIP switches of the electronic clasp locks must be set to ON for
Issue 03 (2021-07-15)
A cabinet electronic clasp lock is installed at the front and rear doors of each
cabinet respectively. The address for the cabinet electronic clasp lock on the
front door is an odd number, and that for the cabinet electronic clasp lock on
the rear door is an even number.
The cabinet electronic clasp locks of odd-numbered cabinets are connected in
series. The addresses start from 1, and a maximum of 12 cabinet electronic
clasp locks can be connected in series.
The cabinet electronic clasp locks of even-numbered cabinets are connected
in series. The addresses start from 1, and a maximum of 12 cabinet electronic
clasp locks can be connected in series.
Set a device address for a cabinet electronic clasp lock by operating the DIP
switch on the cabinet electronic clasp lock. DIP switches 1 to 6 specify the
device address in binary mode. ON indicates 1, and OFF indicates 0.
NO TICE
cabinets at the ends.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
168