Huawei FusionModule2000-S User Manual page 175

Smart modular data center
Hide thumbs Also See for FusionModule2000-S:
Table of Contents

Advertisement

FusionModule2000-S Smart Modular Data Center
User Manual
3.
Step 3 Check the T/H sensor functions.
Table 5-26 Function commissioning
Check Method
Check the running
information about the T/H
sensor on the WebUI.
Set T/H sensor alarm
thresholds.
Issue 03 (2021-07-15)
Table 5-25 Adding a T/H sensor
Path
Parameter
Choose
Device
System
Attribute
Settings >
Device Type
Device
Management
and click Add
Connect To
Device. The
parameters
Communica
for adding
tions Port
devices are
displayed.
Device
Address
Click Test Connect to check whether the T/H sensor connects to the ECC800-
Pro properly.
If the connection is normal, click Confirm. The connected devices are
displayed in the Number of connected devices list.
If the connection is abnormal, check whether the device is properly
connected to the ECC800-Pro, whether the device and the ECC800-Pro are
running properly, and whether the parameter settings are consistent with
the device parameters.
Copyright © Huawei Technologies Co., Ltd.
Value
Select Sensor from the drop-down list box.
Select T/H sensor from the drop-down list
box.
Select ECC800 from the drop-down list box.
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the T/H sensor
is connected to the COM3 port on the ECC800-
Pro. If the T/H sensor is connected to another
port, enter the number of the connected port.
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the T/H sensor based on the
actual situation.
Normal Connection Status
Choose Monitoring > Aisle > T/H Sensor Group
> T/H Sensor n > Running Info, and check the
current temperature, humidity, and NTC
information of the cabinet.
Choose Monitoring > Aisle > T/H Sensor Group
> T/H Sensor n > Running Parameters, and set
High temperature alarm threshold, Low
temperature alarm threshold, High humidity
alarm threshold, Low humidity alarm
threshold, NTC1–6 high temperature alarm
threshold and NTC1–6 low temperature alarm
threshold as required.
5 Power-On Commissioning
166