FusionModule2000-S Smart Modular Data Center
User Manual
●
Issue 03 (2021-07-15)
NO TE
The display of a single-phase module is used as an example.
–
After the PDU2000-M (C) is powered on, the LCM displays the
initialization screen.
Figure 5-6 PDU2000-M (C) initialization screen
–
Press MENU to enter the device communications address screen.
Figure 5-7 PDU2000-M (C) communications settings
–
Press DOWN and UP to select the address to be set.
–
Press MENU to confirm the settings.
NO TE
The parameter settings take effect only if you press MENU and then the
PDU2000-M (C) buzzes and restarts. If you do not press MENU, the PDU2000-M
(C) buzzes and restarts automatically after 30s and the settings are not saved.
Set the PDU2000-M (H) monitoring parameters.
NO TE
The display of a single-phase module is used as an example.
–
After the PDU2000-M (H) is powered on, press MENU. The LCM displays
.
–
Press MENU again to access the device communications address screen.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning