FusionModule2000-S Smart Modular Data Center
User Manual
Issue 03 (2021-07-15)
Item
Generator Usage
Power supply
priority
On the main menu screen, select device configuration and press
the device configuration screen, you can set thresholds for parameters.
The following table lists the system configuration attributes and values.
Table 5-2 System configuration attributes and values
Item
Voltage
Thresholds
Frequency
Thresholds
Modbus
Copyright © Huawei Technologies Co., Ltd.
Value
No Generator; Generator In
Use
Line 1-Switch I; Line 2-
Switch II; No Line Priority
Value
Volt Threshold
–30% to –5%
Min LN1
Volt Threshold
–30% to –5%
Min LN2
Volt Threshold
+5% to +30%
Max LN1
Volt Threshold
+5% to +30%
Max LN2
Freq Threshold
–10% to –1%
Min LN1
Freq Threshold
–10% to –1%
Min LN2
Freq Threshold
+1% to +10%
Max LN1
Freq Threshold
+1% to +10%
Max LN2
– Modbus
– Local /
5 Power-On Commissioning
Description
The default value is No
generator. Set the
parameter based on
site requirements.
The default value is
Line 1-Switch I. Set the
parameter based on
site requirements.
Description
The step increase
is ±1%. The
default settings
are –10% for
LN1 and LN2.
The step increase
is ±1%. The
default settings
are +10% for
LN1 and LN2.
The step increase
is ±1%. The
default settings
are -5% for LN1
and LN2.
The step increase
is ±1%. The
default settings
are +5% for LN1
and LN2.
There is no need
address
to reset the
parameter.
Remote
. On
121