Huawei FusionModule2000-S User Manual page 178

Smart modular data center
Hide thumbs Also See for FusionModule2000-S:
Table of Contents

Advertisement

FusionModule2000-S Smart Modular Data Center
User Manual
Table 5-28 Setting a device address
Address
1
2
3
4
5
6
7
8
9
10
11
12
Step 4 Add a cabinet electronic clasp lock.
1.
2.
3.
4.
Issue 03 (2021-07-15)
DIP
DIP
Switch 1
Switch 2
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
Log in to the ECC800-Pro WebUI as an administrator.
Create a cabinet view in Smart Module View on the home page.
Add a cabinet electronic clasp lock.
Table 5-29 Adding a cabinet electronic clasp lock
Path
Choose System Settings
> Device Management
and click Add Device.
The parameters for
adding devices are
displayed.
Click Test Connect to check whether the connection between the cabinet
electronic clasp lock and the ECC800-Pro is normal.
If the connection is normal, click Confirm. The connected devices are
displayed in the Number of connected devices list.
Copyright © Huawei Technologies Co., Ltd.
DIP
DIP
Switch 3
Switch 4
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
ON
Parameter
Setting
Name
Device
Cabinet electronic clasp lock
Attribute
Device Type
Cabinet electronic clasp lock
Connect To
ECC800-Pro
Communicat
Odd-numbered cabinets: COM2
ions Port
Even-numbered cabinets: COM3
Device
Enter the actual device address of
Address
the cabinet electronic clasp lock.
5 Power-On Commissioning
DIP
DIP
Switch 5
Switch 6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF