● The BCB off alarm (the red indicator is steady on) is displayed on the SmartLi
● The green indicator blinks intermittently. After 1 minute, the BCU starts. The
● If multiple SmartLi cabinets are combined, press and hold the POWER ON/OFF
Step 3 Set the language, time, date, network parameters, and system parameters on the
Settings Wizard screen of the SmartLi.
Figure 5-5 Settings Wizard
Issue 03 (2021-07-15)
NO TICE
LCD. No action is required. After the battery circuit breaker is switched on, the
alarm is automatically cleared.
green indicator blinks at super short intervals and the red indicator is steady
on.
button on the BCU of the master cabinet for more than 2s to power on the
master cabinet. Then, power on slave cabinets one by one in the same way.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
129