ECC800 Data Center Controller
SmartDC V100R021C10
User Manual
Issue
04
Date
2021-10-09
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei SmartDC V100R021C10

  • Page 1 ECC800 Data Center Controller SmartDC V100R021C10 User Manual Issue Date 2021-10-09 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    Indicates a hazard with a medium level of risk which, if not avoided, could result in death or serious injury. Indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 4 Logic. Added 8.7.22 How Can I Set NetCol8000-A Parameters (Modbus- TCP)?. Updated 8.41.2 How Can I Prepare and Log in the App?. Deleted the content related to the mobile phone app. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 5 Power Distribution Devices in the Power Module. Updated 6.19 Intelligent Networking of FusionModule2000 Busways. Updated 8.7.17 How Do I Set and Add an Electricity Meter?. 2021-01-06 This issue is used for first office application (FOA). Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 6: Table Of Contents

    3.2.4.1.4 Card Reader with a Keypad.............................40 3.2.4.1.5 Magnetic Lock................................40 3.2.4.2 Cabinet Access Control System..........................41 3.2.4.3 Cabinet Electronic Clasp Lock............................ 43 3.2.5 Smart Module Actuator..............................44 3.2.6 AC Actuator..................................48 3.2.7 Skylight Actuator................................50 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 7 5.8 Commissioning the PDU2000 (for FusionModule500/800).................120 5.9 Commissioning Cabinet Electronic Clasp Locks....................... 123 6 Feature Description......................127 6.1 Setting Device Performance Parameters........................127 6.2 Setting ECC800-Pro Cascading............................128 6.3 Commissioning a UIM20A Expansion Module......................129 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 8 6.6.1.3 (Optional) Commissioning an Intelligent Aisle Light..................216 6.6.1.4 Linking the Smoke Alarm with Skylight Open....................220 6.6.1.5 High-Density Island Linkage............................ 222 6.6.2 FusionModule500/800 Linkage Control........................224 6.6.2.1 Link Air Conditioner Fault with Emergency Fan....................226 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 9 6.13.4 Maintaining the Facial Data............................. 263 6.14 Remote Management..............................263 6.14.1 NetEco Management..............................263 6.14.1.1 Connecting a Communications Cable........................ 263 6.14.1.2 Setting NetEco Parameters............................ 265 6.14.1.3 Creating an ECC800-Pro on the NetEco......................267 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd. viii...
  • Page 10 8.7.15 How Can I Set and Add an rPDU?.......................... 319 8.7.16 How Can I Set and Add an ATS?..........................322 8.7.17 How Do I Set and Add an Electricity Meter?...................... 323 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 11 8.17 How Can I Export Historical Data and Device Data?..................361 8.18 How Can I Export or Import a Configuration File?....................362 8.19 How Can I Export Fault Information?........................363 8.20 How Can I Synchronize Device Parameters?......................364 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 12 8.41.6 How Can I Synchronize Device Parameters?....................... 389 8.41.7 How Can I Handle App Login Failure?........................390 9 PLC Function.........................391 9.1 Linkage Control Introduction............................391 9.2 Linkage Control Configuration Examples........................392 10 Acronyms and Abbreviations..................395 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 13: Safety Information

    The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this document do not cover all the safety instructions. They are only supplements to the safety instructions. Huawei will not be liable for any consequence caused by the violation of general safety requirements or design, production, and usage safety standards.
  • Page 14 ● Keep irrelevant people away from the equipment. Only operators are allowed to access the equipment. ● Use insulated tools or tools with insulated handles, as shown in the following figure. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 15 Do not change the structure or installation sequence of equipment without permission. ● Do not touch a running fan with your fingers, components, screws, tools, or boards before the fan is powered off or stops running. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 16: Personnel Requirements

    Do not power on the equipment before it is installed or confirmed by professionals. 1.2 Personnel Requirements ● Personnel who plan to install or maintain Huawei equipment must receive thorough training, understand all necessary safety precautions, and be able to correctly perform all operations. ●...
  • Page 17 0°C. Handle cables with caution, especially at a low temperature. – Cables stored at subzero temperatures must be stored at room temperature for at least 24 hours before they are laid out. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 18: Installation Environment Requirements

    Install the equipment in an area far away from liquids. Do not install it under areas prone to condensation, such as under water pipes and air exhaust vents, or areas prone to water leakage, such as air conditioner vents, ventilation Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 19 Any violations must be promptly pointed out by the site manager or safety supervisor and the involved personnel should be prompted for correction. Personnel who fail to stop violations will be forbidden from working. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 20: Mechanical Safety

    Ensure that the wider end of the ladder is at the bottom, or protective measures have been taken at the bottom to prevent the ladder from sliding. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 21 When pulling the equipment out of a cabinet, be aware of unstable or heavy objects on the cabinet to prevent injury. ● Be cautious to avoid injury when moving heavy objects. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 22: Others

    To protect loads during UPS upgrade, set the output to maintenance bypass mode. To avoid load power failure or damage, ensure that the bypass input is within the specified power supply range. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 23: Overview

    – Supports the function of transparent transmission over the RS485 port, so that southbound components can communicate with the NetEco after accessing the ECC800-Pro. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 24 Supports cabinet-level magnetic locks, door status sensors, and temperature monitoring, providing high security. – Connects to the NetEco and supports SNMP to implement centralized management of multiple modules in multiple scenarios. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 25: Device Description

    ● In configuration 2, install power modules in slots 1 and 2. Figure 3-1 ECC800-Pro collector in configuration 2 (1) Slot 1: power modules (2) Slot 2: power modules (3) Slot 3: main control module Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 26 Power Port The ECC800-Pro provides four power ports, including two AC input ports (AC_INPUT1 and AC_INPUT2) and two DC output ports (DC_OUT1 and DC_OUT2). Table 3-3 provides the power port pin definitions. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 27: Main Control Module

    (14) DO/12V (15) RF_Z (802.15.4) (16) WLAN (reserved) (17) 4G (18) SW button NO TE The WLAN port is reserved and cannot be connected to a WLAN antenna for WLAN communication. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 28 ● Four RS485 ports with the default communications rate of expansion 9600 bit/s ● COM1–COM3 ports provide 12 V DC power. ● The power supply can be switched on or off and is on by default. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 29 SIM card slot is provided to use the 4G SIM card of China Unicom, China Mobile, or China Telecom. NOTE The prerequisite for using a SIM card is that the site has signal coverage. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 30 ● Restores the default IP address, factory settings, and user information. ● Supports RF_Z (802.15.4) networking. Table 3-5 ECC800-Pro RF_Z parameters Item Specifications RF_Z operating 2405–2480 MHz frequency RF_Z EIRP (max.) 8 dBm Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 31 Table 3-7 GE port pin definitions Item Description Pin 1 GE1+ sequence Pin 2 GE1- Pin 3 GE2+ Pin 4 GE3+ Pin 5 GE3- Pin 6 GE2- Pin 7 GE4+ Pin 8 GE4- Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 32 Table 3-9 COM3/12V port pin definitions Item Description Pin 1 RS485+ sequence Pin 2 RS485- Pin 3 12V DC_OUT Pin 4 RS485+ Pin 5 RS485- Pin 6 Pin 7 Pin 8 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 33 Table 3-11 AIDI_1, AIDI_2 and AIDI_3 ports pin definitions Item Description Pin 1 Type_1 sequence Pin 2 Type_2 Pin 3 12V DC Pin 4 Type_3 Pin 5 Type_4 Pin 6 Pin 7 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 34 ● Steady on: The 12 V DC output is normal. ● Off: No 12 V DC output is provided. Table 3-13 USB port pin definitions Item Description Pin sequence Pin 1 Pin 2 Pin 3 Pin 4 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 35 The RF_Z indicator is network RF_Z pairing mode, press and hold down blinking at super (802.15.4) the button for 3s to 5s to enter the short intervals. pairing wireless network pairing mode. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 36: Power Module

    4 Hz, on for 0.125s and then off for 0.125s). Yellow Alarm Steady on Power limiting warning due to indicator ambient overtemperature; protection shutdown alarm due to ambient overtemperature or undertemperature Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 37: Southbound Device Introduction

    1s). Fault Steady on The module locks out due to indicator output overvoltage. The module has no output due to internal faults. The module is normal. 3.2 Southbound Device Introduction Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 38: Uim20A Expansion Module

    (2) COM_OUT (reserved) (3) COM_IN (reserved) Table 3-17 Structural specifications of the UIM20A expansion module Item Specifications Width 120 mm Depth 200 mm Height 43 mm Operating –30°C to +65°C temperature Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 39 Communications Ports The following table describes the pin definitions for ports COM1/AIDI_1 to COM8/ AIDI_8. Table 3-19 Pin definitions for ports COM1/AIDI_1 to COM8/AIDI_8 Item Description Pin1 RS485+ sequence Pin2 RS485- Pin3 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 40 Hz), on for 1s and then off for 1s). Blinking The communication is interrupted or the ECC800-Pro is at short unsuccessfully registered (blinking at 2.5 Hz, on for 0.2s intervals and then off for 0.2s). Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 41: Rack Environment Unit

    (5) COM2/12V port (6) COM3 port (7) COM4 port (8) NTC1–3 (9) NTC4–6 (10) AI/DI_1 port (11) AI/DI_2 port (12) 12V_1 port (13) 12V_2 port (14) BLINK button (15) Status indicator Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 42 0.5 Hz, on for 1s and then off for 1s). Blinking at PoE communication fails (the short indicator blinks at 4 Hz, on for intervals 0.125s and then off for 0.125s). Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 43: Smart Eth Gateway

    (4) POE_3–4 ports power port signal port (5) 48V_OUT1 power (6) 48V_OUT2 power (7) FE_2 cascading (8) PWR_OUT output port output port signal port cascading power port (9) BLINK button (10) Status indicator Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 44 The smart ETH gateway indicator long successfully registers with intervals the ECC800-Pro and the software runs properly (the indicator blinks at 0.5 Hz, on for 1s and then off for 1s). Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 45: Access Control System

    Item Specifications Chip model Chip name Mifare 1K (S50) card Chip type Philips Mifare 1 IC S50 Operating frequency 13.56 MHz Read/write distance 1–3 cm Storage capacity 8 kbit, 16 partitions Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 46: Access Actuator

    (10) AI/DI_2 dry contact (11) AI/DI_1 dry contact (12) LOCK/GND/GATE/COM door (reserved port for linkage (reserved port for exit status or magnetic lock port control or third-party fire button) extinguishing system dry contacts) Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 47 Supported Indicators Table 3-29 Access actuator indicators Indicator Color Name Status Green Power input ● Steady on: The power input is normal. status ● Off: There is no power input. indicator Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 48 The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/ COM). Table 3-30 lists the LOCK/GND/GATE/COM port pin definitions. Table 3-30 LOCK/GND/GATE/COM port pin definitions Item Description LOCK/GND LOCK 12V_OUT (control magnetic Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 49: Fingerprint And Card Reader With A Keypad

    Rated operating current 300 mA±15% Card type supported IC card Authorized storage A maximum of 3000 authorized users, with a maximum of 6000 fingerprints Communications mode RS485 and Wiegand communications ports Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 50: Fingerprint And Card Reader

    The indicator blinks blue, red, and blue in order. Buzzer sounds The buzzer sounds once. 3.2.4.1.3 Fingerprint and Card Reader Figure 3-12 Fingerprint and card reader (1) Fingerprint reader (2) LED indicator Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 51 Fingerprint reader The indicator turns on (white). Buzzer sounds The buzzer sounds once. Card swiping LED indicator The indicator blinks blue, red, and blue in order. Buzzer sounds The buzzer sounds once. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 52: Card Reader With A Keypad

    Static standby current: 80 mA; dynamic operating current (card swiping, key pressing): 150 mA; minimum input current: 12 V DC/300 mA Communication mode Wiegand communications port 3.2.4.1.5 Magnetic Lock Figure 3-14 Double-door magnetic lock Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 53: Cabinet Access Control System

    The system displays the status of cabinet doors and locks in real time, the system displays the status of cabinet doors and locks in real time and reports the unauthorized door opening. ● The system supports remote unlocking. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 54 The user can set a password. ● A password should contain at least three digits. ● The password can be reset if the user forgot it. Figure 3-18 Mechanical code lock Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 55: Cabinet Electronic Clasp Lock

    (1) LED indicator (2) DIP switch (3) RJ45 power port Table 3-37 RJ45 port definitions Pin Description Description RS485+ RS485+ RS485- RS485- +12 V power supply +12VDC RS485+ RS485+ RS485- RS485- Ground Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 56: Smart Module Actuator

    In addition, the smart module actuator manages access rights, records entrance and exit events, and records alarms. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 57 5 A. ● AC OUT2: one AC output, 90 V AC to 240 V AC. The maximum current is 5 A. LAN port FE communication with a communications rate of 10/100 Mbit/s Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 58 ● Hold down the button for more than 6 seconds to clear network parameters. Address DIP 4-pin address DIP switch (reserved) switch Fuse 16 A, 250 V AC Spare fuse box Two 16 A, 250 V AC fuses E-label Supported Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 59 1s and then off for 1s). Blinking at A network is being set up, super short and node access is allowed intervals (the indicator blinks at 10 Hz, on for 0.05s and then off for 0.05s). Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 60: Ac Actuator

    PAD (AC OUT2). Figure 3-21 AC actuator (1) AC OUT2 port (2) AC OUT1 port (3) AC IN port (4) Status indicator (5) BLINK button (6) AIDI_1 and AIDI_2 (7) COM1 and COM2 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 61 Blinking at The AC actuator successfully long registers with the ECC800-Pro intervals and the software runs properly (the indicator blinks at 0.5 Hz, on for 1s and then off for 1s). Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 62: Skylight Actuator

    The skylight actuator controls the rotating skylight on the aisle containment of the smart module through the alarm linkage information from the fire extinguishing system or the control information from the upper computer. The skylight actuator supports E-labels and wireless networking (802.15.4). Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 63 Two AI/DI ports for detecting fire extinguishing linkage signals; smoke detection signals also supported DO output One 12 V DC power output for controlling the skylight magnetic lock; driving nine skylight magnetic locks simultaneously Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 64 (blinking at 10 Hz, on for 0.05s and then off for 0.05s) and then turns off for 0.5s. The cycle lasts for 5s. Alarm Steady on A system failure alarm is indicator generated. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 65: Multi-Functional Sensor

    The multi-functional sensor can connect to the ECC800-Pro over FE or wireless communication. NO TE The infrared detection function is enabled only when the intelligent lighting function is enabled. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 66 ● If the sensor is connected to network, after you hold down the button for 2s to 3s, the RUN indicator blinks. ● Hold down the button for more than 6 seconds to clear network parameters. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 67 Blinking at A network is set up, and no long node access is allowed (the intervals indicator blinks at 0.5 Hz, on for 1s and then off for 1s). Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 68: Smoke Sensor

    < 95% RH (non-condensing) Dimensions Diameter: 112 mm, height: 41 mm 3.2.10 Temperature Sensor The temperature sensor (BOM number: 33010348) is used for the surface temperature measure, industrial process control, measurement instrument, etc. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 69: Cabinet Temperature Sensor

    Storage temperature –40°C to +70°C 3.2.11 Cabinet Temperature Sensor Figure 3-26 Cabinet temperature sensor Table 3-50 Technical specifications of a cabinet temperature sensor Item Specifications Temperature detection –20°C to +70°C range Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 70: Alarm Beacon

    Table 3-51 Structural specifications of an alarm beacon Item Specifications Dimensions (L x W x 130 mm x 75 mm x 55 mm Installation Installed on a wall requirements Environmental RoHS, Reach protection Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 71: Optional) Smart U Space Manager

    Communication Rate: 9600 bit/s Communication format: one start bit, eight data bits, no parity bit, one stop bit Power input 12 V DC±5% (RJ45) Rated current and power 250 mA consumption Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 72: Elight Actuator

    Steady on Associated alarm severity is set to None. Other color Steady on The device is abnormal or cables are incorrectly light or blinking connected to terminals R, G, and B. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 73: Water Sensor

    3.2.15.1 WLDS600 Water Sensor The WLDS600 water sensor consists of a water detection cable, a water detector with the BOM number of 33010556, an extension line, and a conversion cable. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 74 Modbus-RTU, data bits 8 bits, no parity Baud rate, Default support 9600, baud rate configurable, address address configurable, default address is 1, stop bit is 1 bit. Detected 100 m (support cable connection in series) distant Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 75: Wlds900 Water Sensor

    (3) Conversion cable the water detector (4) Conversion cable (5) Water detection cable end A, (6) Water detection cable end B, connected to the connected to the conversion cable water detection cable Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 76: Electrode Water Sensor

    –40°C to +80°C temperature Storage –40°C to +80°C temperature Service life 10 years 3.2.16 WiFi Module The WiFi module provides WiFi signals for equipment such as PADs to interact with the host computer. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 77 USB 2.0 Hi-Speed connector Voltage range 5.0 V DC±5% Operating –20°C to +70°C temperature Storage –40°C to +90°C temperature Relative 10%–90% RH (non-condensing) humidity Storage 5%–90% RH (non-condensing) humidity Power < 0.8 W Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 78: Eth Converter

    If you press the BLINK button, the RUN indicator blinks button intermittently at super short intervals (blinking at super short intervals for 0.5s and then off for 0.5s) for 10 seconds. E-label Supported Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 79: Pad

    The PAD allows the wireless access from the data center management system. You can monitor the equipment in the data center and environmental parameters in real time over the app. The recommended model is T5-10. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 80 ● Extension card: Micro SD, a maximum of 256 GB (non-standard configuration) Button/Port ● Touch button + power switch and volume button ● 3.5 mm stereo headphones port ● Micro SD card port ● MicroUSB port Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 81: T/H Sensor

    ● Power adapter charge time: about 3.5 hours (5 V 2 A adapter) 3.2.19 T/H Sensor 3.2.19.1 T/H Sensor (BOM Number: 33010346) Figure 3-36 Appearance The T/H sensor uses an RJ45 connector. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 82 Temperature accuracy ±1°C Humidity measuring range 5%–95% RH Humidity precision ±5% RH (25°C, 20%–80% RH) Operating temperature –20°C to +70°C Operating voltage 9–16 V DC Storage temperature –40°C to +70°C Output RS485 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 83: T/H Sensor (Bom Number: 02310Nbs)

    Pin5 or Pin 6 Table 3-67 T/H sensor specifications Item Specifications Temperature measuring range –20°C to +70°C Temperature accuracy ±1°C Humidity measuring range 5%–95% RH Humidity precision ±5% RH (25°C, 20%–80% RH) Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 84: Ambient T/H Sensor (Bom Number: 33010516)

    The appearance of the T/H sensor depends on the onsite delivery. Figure 3-41 Pins of an RJ45 connector Table 3-68 RJ45 port pin definitions Description Pin1 or Pin 4 Pin2 or Pin 5 Pin3 Pin6 Pin7 Reserved Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 85: T/H Sensor (Bom Number: 02311Fqg)

    Storage temperature –40°C to +70°C Output RS485 3.2.19.4 T/H Sensor (BOM Number: 02311FQG) Figure 3-42 Appearance (1) RS485-OUT (2) RS485-IN (3) DIP switch (4) Button (5) NTC1–3 (6) NTC4–6 (7) Display Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 86: T/H Sensor (Bom Number: 02312Pbl)

    Storage temperature –40°C to +70°C Output RS485 3.2.19.5 T/H Sensor (BOM Number: 02312PBL) Figure 3-43 Appearance (1) RS485-OUT (2) RS485-IN (3) DIP switch (4) Button (5) NTC1–3 (6) NTC4–6 (7) Display Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 87: Infrared Remote Control Module

    Table 3-72 Technical specifications of the infrared remote control module Item Specifications Number of supported ≤ 4 remote control commands Communication Interworks with the monitoring system over Modbus-RTU to implement remote control. The baud rate can be 9600 bit/s. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 88: Intelligent Battery Monitoring System

    (Optional) When a battery system needs to be managed by multiple iBOXs, the iBOXs can be connected to northbound devices using straight-through cables (the ECC800-Pro supports four iBOXs in parallel through the smart ETH gateway) without cascading. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 89: Ibox

    It collects battery status data from the downstream iBAT groups through wireless communication, and sends the data to the ECC800-Pro, UPS, and the third-party network management system (NMS) through COM or PoE ports. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 90 (14) RF_Z indicator (15) Delivered antenna Figure 3-47 iBOX bottom view (1) Fastener (2) Micro SD card slot (3) Default button (IP reset) (4) ADDR dual in-line package (DIP) switch (RS485 communications address) Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 91 Table 3-74 –48 V, 0.5 A port pin definitions Definition Description The system provides 48 V DC operating voltage – in this scenario. PoE Port Figure 3-49 PoE port pins Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 92 4, 5 P45_P1 RX– 7, 8 P78_P1 COM Port Figure 3-50 COM port pins Table 3-76 COM port pin definitions Signal Description RS485+ Two cascaded RS485 communication ports RS485– RS485+ RS485– Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 93 Figure 3-51 HALL current monitoring port pins Table 3-78 Pin definitions for HALL current monitoring ports Definition Description +12V Detect the charge and discharge currents of –12V four battery strings or eight battery routes. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 94 Monitors ● Grounded: The Disconnect routes. the battery battery circuit circuit breaker is ON. breaker ● Disconnected: The battery circuit breaker is OFF. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 95 BCBs are circuit circuit connected breaker is breaker to the input. status ● Disconnect ed: The battery circuit breaker is OFF. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 96 Indicators Table 3-82 Indicators Indicat Color Meaning Status Description Measure RF_Z Green Wireless Steady on No network Requires no communi parameters handling. cation exist. (A status network is to be created.) Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 97 3 minutes.) ● If no, go to the next step. 2. Check whether the device is malfunctioning. ● If yes, replace the device. ● If no, contact the technical support. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 98 Creates a network if no network button for more has been created. Switches than 1s but less between network organization and than 5s. data transmission if a network has been created. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 99: Ibat

    ● Supports the hibernation function. (When it detects that the battery voltage is low, it will enter the low-power mode.) ● Communicates with the iBOX wirelessly. iBAT Appearance Figure 3-53 iBAT2.0 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 100 (The iBAT is waiting to connect to a network.) Blinking at ● Network parameters are super short being cleared. intervals ● The iBAT is blinking. (iBattery 2.0) Blinking at short intervals (iBattery 3.0) Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 101 Initializes the network parameters if there is a network. Button Hold down the Clears the current network and resets holding down button for more the wireless module; disconnects the than 5s. network. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 102: Ui Description

    ECC800 Data Center Controller User Manual 4 UI Description UI Description 4.1 WebUI For data transmission security, the ECC800-Pro supports WebUI access through TLS. Figure 4-1 Home page Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 103 ● IP device num is 100 by Gateway running. For default. Group. example, set ● Online detection timeout smart cooling interval is 30 by default. product parameters, delete devices failing in Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 104 – Query device – Data performance data. Operation – Query operation – logs. Access Event – Query access – control events. Export Data – Export historical – data and device data. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 105 Managemen delete videos. NetEco Set SNMP and Server IP is 192.168.8.11 by Application NetEco default. communications Port number is 31220 by parameters. default. The Network port for link establishment is WAN_1. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 106 Alarm Basic Alarm Set basic alarm – Parameters Parameters parameters and alarm association Alarm – parameters. Linkage Performance Performance Enable or disable – Parameters Parameters the device performance statistics function. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 107 E-Label – Query or export E- – labels. User – Manage users, – Managemen such as adding, modifying, and deleting users. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 108 Mgmt information. Configuratio – Support the – n Wizard deployment wizard and set simple parameters as instructed by the wizard. Life Cycle – Check the service – life of main devices. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 109: Pad App

    ● c: Multi-Module Monitoring is displayed on the Home page only after you set Smart Module Cascading. ● d: If the system type is FusionModule2000 or FusionModule5000, this function is unavailable. ● e: This function is supported only by some devices, such as Huawei smart cooling products and integrated UPSs. 4.2 PAD App...
  • Page 110 Allows you to view device asset details such as electronic Details labels of system devices and other devices. Device Check the Software Version and Hardware Version of the Version device. Info Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 111: Power-On Commissioning

    Step 1 Connect a network cable between the PC network port and the WAN1 port (protected by a security mechanism) on the ECC800-Pro. Table 5-1 Default IP addresses for the WAN and LAN ports on the ECC800-Pro Port Default IP Address WAN1 192.168.8.10 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 112 When you use Internet Explorer for access, set Internet Explorer to ensure the normal display of and operations on the WebUI. Choose Tools > Compatibility View, and add the web access address to the compatibility view. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 113 Choose Tools > Internet options > Security, choose Add the ECC800-Pro IP address to the list of trusted sites. Figure 5-1 Adding an address Enable file download and set the security level of the trusted site to low. Figure 5-2 Setting parameters Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 114 – An account is logged out due to timeout if no operation is performed within 10 minutes after system login. – A maximum of three users can log in to the ECC800-Pro WebUI at the same time. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 115: Performing Startup Password Authentication (For Fusionmodule500/800)

    Before the installation, ensure that the mobile phone is connected to the Internet and the network is running properly. – Huawei AppGallery installed on the mobile phone Log in to the Huawei AppGallery client, search for Service Expert, and tap Install. Huawei AppGallery is preinstalled on Huawei mobile phone by default. –...
  • Page 116 ECC800 Data Center Controller User Manual 5 Power-On Commissioning Table 5-2 Operation methods for the scenario where Huawei AppGallery is not installed on the mobile phone Method Procedure Installation Verification Install the app 1. Log in to Huawei Check that the app...
  • Page 117: Commissioning Configuration Wizard

    ● To exit before the configuration is complete, click Finish to terminate the configuration directly. Step 4 After configuring the parameters, click Finish. Step 5 After confirming that the commissioning Result is normal, enter the Checker Name and Check Date, and click Configuration Completed. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 118: Configuring Event Notification

    If Test email sending failed is displayed, check whether the receiver's email server requires CA certificate verification. If it is required, download the CA certificate from the receiver's email website and upload it in the Mailbox Certificate area. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 119 25 at Password cursor and for 163 Mail, 139 Mail smtp. press Enter Non- 126 Mail, 139.com to obtain encryption: 25 and QQ email server Mail. IP addresses. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 120 Click Test to check whether the added mailbox is available. If it is available, Successfully to send the test email. is displayed. If it is unavailable, Failed to send the test email. is displayed. Check whether the receiver's mailbox parameters for receiving emails are correctly set. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 121 Successfully to send the test short message. is displayed. If it is unavailable, Failed to send the test short message. is displayed. Check whether the mobile phone number is correctly set. Step 5 Set the alarm notification delay parameter and the new alarm notification parameter. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 122 Figure 5-8 Adding alarm notification NO TICE Mailbox Address in Alarm Notification can be selected after it is added in Mailbox Settings. Mobile Phone Number can be selected after it is added in SMS Settings. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 123 3. Check whether the domain name of the email server is correctly configured. Check whether the local network cable is properly connected and whether the network adapter is activated. Ensure that the local network connection is normal. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 124 Check whether the outbox address matches the user name for logging in to the email server. On the outbox configuration page, set Encryption mode to SSL. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 125: Commissioning The Smart Busbar

    Then, you need to set parameters for the general input units and power distribution units; otherwise, a false alarm may be generated. Procedure Step 1 Set parameters for general input units on the ECC800-Pro WebUI. Set parameters for general input unit 1. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 126 System Settings > Signal Name Modify and access the Batch Signal Configuration to modify the name, and then tap Submit. The following is an example of how to display two branches for power distribution unit1. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 127: Commissioning The Elight

    Set the parameters for other power distribution units in the same way or by synchronizing parameters. Path: Maintenance > Parameter Sync ----End 5.6 Commissioning the eLight If an eLight is installed, perform the following steps to configure it. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 128 In the Smart Module View, click Modify Device. Select an eLight actuator under Devices, drag it to the access actuator to which you want to bind the eLight actuator, and click Exit Edit Mode. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 129 To modify the parameters of a single eLight, do as follows: Choose Monitoring > Aisle > eLight Actuator Group > eLight Actuator. The Running Parameters page is displayed. Select the Associated alarm severity as required and click Submit. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 130: Commissioning The Elight (For Fusionmodule500/800)

    Toggle switches 1 to 4 of the DIP switch specify the device address in binary mode. ON indicates 1, and OFF indicates 0. Table 5-11 Setting a device address Address Toggle Toggle Toggle Toggle Switch 1 Switch 2 Switch 3 Switch 4 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 131 Log in to the ECC800-Pro WebUI as an administrator. Choose Monitoring > Aisle > eLight Actuator Group > eLight Actuator. The Running Parameters page is displayed. Select the Associated alarm severity as required and click Submit. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 132: Commissioning The Pdu2000 (For Fusionmodule500/800)

    Step 4 If there are multiple eLights, repeat Step 1–Step ----End 5.8 Commissioning the PDU2000 (for FusionModule500/800) When the system type is FusionModule500/800 and a PDU2000 is installed, perform the following steps to configure it. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 133 After the PDU2000-M (C) is powered on, the LCM displays the initialization screen. Figure 5-10 PDU2000-M (C) initialization screen – Press MENU to enter the device communications address screen. Figure 5-11 PDU2000-M (C) communications settings Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 134 The PDU2000s whose addresses are greater than 20 must be manually added. Table 5-15 Manually adding a PDU2000 Path Parameter Setting Choose Device Select PDU from the drop-down list box. System attribute Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 135: Commissioning Cabinet Electronic Clasp Locks

    Step 2 (Optional) If the cabinet door still cannot be opened after step 1 is performed, adjust the position of the cabinet electronic clasp lock by using the slotted holes until the cabinet door can be opened and closed properly. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 136 Step 4 Add cabinet electronic clasp locks. Log in to the ECC800-Pro WebUI as an administrator. Create a cabinet view in Smart Module View on the home page. Add a cabinet electronic clasp lock. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 137 Monitoring > Controls tab. back door from the Cabinet cabinet Cabinet > IT door control drop-down list box, electroni Cabinet101 and click Submit to remotely c clasp open the door. lock Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 138 Submit. The cabinet batches electronic clasp locks unlock the doors in batches based on the signal value. a: Cabinet electronic clasp lock 1 of IT cabinet 101 is used as an example. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 139: Feature Description

    Step 2 Click the Performance Parameters(enable) tab, select a device in Device Type, and click OK. All enabled performance indicators are displayed in the result list. Step 3 You can set the status of enabled performance indicators to Disable as required. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 140: Setting Ecc800-Pro Cascading

    ECC800-Pros. Then, you can log in to view the details. Procedure Step 1 Log in to the ECC800-Pro WebUI as an administrator. Step 2 Choose System Settings > Smart Module Cascading. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 141: Commissioning A Uim20A Expansion Module

    Step 1 Log in to the ECC800-Pro WebUI as an administrator. Step 2 Choose System Settings > Device Management, and click Auto Discover Device to add the device. Devices connected to the UIM can be identified. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 142 In this scenario, only one type of intelligent devices is monitored in each cabinet. The port for connecting the intelligent device to the UIM20A must meet the physical connection rules in Table 6-3. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 143 Table 6-4 Cable connection mode in a temperature map scenario COM Port COM1 COM3 COM5 COM7 Connected T/H sensor T/H sensor T/H sensor T/H sensor Device group group group group COM Port COM2 COM4 COM6 COM8 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 144 Hold down the BLINK button on the UIM for less than 2s. The RUN indicator on the UIM blinks fast, and the cabinet corresponding to the UIM blinks in the smart module view. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 145: Access Management

    Set Door1 sensor type to Door sensor, ensure that Door1 power supply is Yes, and click Submit. Perform the preceding operations to set parameters for ports AI/DI_2 to AI/ DI_8. Step 2 Check the door status sensor functions. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 146: Commissioning A Door Status Sensor (Connected To The Ai/Di Port On The Rack Environment Unit)

    If the alarm is enabled for the front and rear door. doors, a cabinet door open alarm is displayed on the active alarm screen of the app or the active alarm page of the WebUI. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 147: Commissioning A Door Status Sensor (Connected To The Ai/Di Port On The Uim20A Expansion Module)

    Step 2 Check the door status sensor functions. Table 6-8 Function check Check Method Normal Connection Status Open the cabinet door. Door1 DI alarm is generated on the active alarm page of the app or WebUI. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 148: Commissioning The Door Status Sensor (Connected To The Ecc800-Pro)

    Step 3 If there are more than two cabinets, set the door status sensor parameters. Set door status sensor parameters for the IT cabinet by referring to step 1. Choose System Settings > Signal Name Modify. The Batch Signal Configuration page is displayed. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 149: Commissioning An Access Control Device And A Cabinet Electronic Lock Or Fingerprint Lock

    Click Authentication Mode and set the authorization mode for the FusionModule Actuator or access actuator. Select Card, Fingerprint, Card and password, Card and fingerprint, Fingerprint and password, Card, password and fingerprint or Card, password or fingerprint. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 150 Click Add on the Authorization Operations tab page. The New User page is displayed. NO TE The system supports a maximum of 1000 access users. On the Basic Info tab page, enter User name and Employee ID. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 151 The cabinet fingerprint lock does not support access user registration. Access users can be registered only on the aisle access control device, and the registered information is sent to the cabinet fingerprint lock through the ECC800-Pro. Figure 6-4 Recording fingerprints Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 152 Click OK to complete the task of adding access management settings. On the Authorization Operations tab page, click Synchronize to Device, select the modified access control devices, and click Start Synchronization. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 153 Low level alarm for Logical level configuration for reader removed. Step 3 Check the functions of the access control device and access actuator. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 154 Method 3: If the time after the electronic lock of the cabinet is opened exceeds the value of Door open timeout, a Door open time-out alarm is generated. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 155: Commissioning The Exit Button, Skylight Button, Atmosphere Light, Emergency Button, And Magnetic Lock

    Normal Connection Status Attempt to open the door by pressing The aisle door is opened successfully. the exit button when the aisle door is closed. Step 2 Check functions of the skylight button. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 156 ECC800-Pro. closed, relocate the open alarm on the magnetic lock and magnet ECC800-Pro. to minimize the deviation until the door open alarm is cleared. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 157: Commissioning An Emergency Door Release Button

    Before commissioning a camera, prepare the following documents in addition to this document. Table 6-19 Documentation for commissioning Component Document IPC6325-WD-VR Configuration Guide IPC6325-WD-VR C3220 Huawei C Series SDC 8.0.1 Product Documentation VCN500/VCN510/ VCN500: VCN500 Product Documentation VCN520/VCN540 VCN510/VCN520/VCN540: VCN510&VCN520&VCN540 Product Documentation IVS1800 IVS1800 8.1.0 Product Documentation 6.5.2 Networking Scenarios...
  • Page 158: Commissioning A Camera (Smart Eth Gateway Networking Scenario)

    VCN or IVS1800. Figure 6-9 Camera + VCN or IVS1800 connecting to the LAN switch 6.5.3 Commissioning a Camera (Smart ETH Gateway Networking Scenario) Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 159: Commissioning An Ipc6325 Camera

    Use a network cable to connect the PC to the PoE port on the smart ETH gateway. Then, set the local IP address of the PC to 192.168.0.11. Remove the camera shell and press the reset button for 6s to 10s to restart the camera. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 160 1. Choose Tools > Internet Options. The Internet Options dialog box is displayed. 2. Click the Connections tab. 3. Click LAN Settings. 4. Deselect Use a proxy for your LAN. 5. Click OK. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 161 2. Click the Security tab. 3. Select Internet. 4. Click Custom level. The Security Settings-Internet Zone dialog box is displayed. 5. Set Use Pop-up Blocker to Disable. 6. Click OK. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 162 Click the link under Link to access and log in to the camera WebUI. Enter the preset user name admin and the preset password HuaWei123, and click Log Figure 6-12 Clicking the camera access link Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 163 ONVIF interface of the IP camera, enter the new password in Password. Otherwise, the ECC800- Pro cannot collect motion detection alarms from the IP camera. Figure 6-14 Adding video information Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 164 Choose Settings > Video/Audio/Image > Video, and set camera stream type, primary stream, and secondary stream 1 parameters, as shown in the following figures. NO TICE Set the encoding protocol to H.265. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 165 ECC800 Data Center Controller User Manual 6 Feature Description Figure 6-16 Setting primary stream parameters Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 166: Commissioning An Ipc6325 Camera (Sd Card Configured)

    Figure 6-17 Setting secondary stream 1 parameters ----End 6.5.3.2 Commissioning an IPC6325 Camera (SD Card Configured) Context If the VCN or IVS1800 is not configured and an SD card is chosen, perform the following procedure. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 167 ECC800 Data Center Controller User Manual 6 Feature Description Procedure Step 1 Log in to the Huawei IPC WebUI. Step 2 Format the SD card. Choose Settings > System Configuration > Storage Management. The Storage Management page is displayed. Format the SD card.
  • Page 168 Figure 6-19 Setting motion detection parameters Step 5 Set the deployment policy. Figure 6-20 Setting the deployment policy Step 6 Set the alarm linkage policy. Figure 6-21 Setting the alarm linkage policy ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 169: Commissioning A C3220 Camera

    Use a network cable to connect the PC to the PoE port on the smart ETH gateway. Then, set the local IP address of the PC to 192.168.0.11. Remove the camera shell and press the reset button for 6s to 10s to restart the camera. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 170 1. Choose Tools > Internet Options. The Internet Options dialog box is displayed. 2. Click the Connections tab. 3. Click LAN Settings. 4. Deselect Use a proxy for your LAN. 5. Click OK. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 171 2. Click the Security tab. 3. Select Internet. 4. Click Custom level. The Security Settings-Internet Zone dialog box is displayed. 5. Set Use Pop-up Blocker to Disable. 6. Click OK. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 172 Click the link under Link to access and log in to the camera WebUI. Enter the preset user name admin and the preset password HuaWei123, and click Log Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 173 External IP: Enter the external IP address of the camera or VCN (the actual IP address planned by the customer prevails). ● Internal IP: Enter the internal IP addresses of the camera and VCN or IVS1800, for example, 192.168.248.56. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 174 Password. Otherwise, the ECC800-Pro cannot collect motion detection alarms from the IP camera. Figure 6-27 Adding video information Figure 6-28 Password for accessing the IP camera ONVIF interface Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 175 Choose Settings > Video/Audio/Image > Video, and set camera stream type, primary stream, and secondary stream 1 parameters, as shown in the following figures. NO TICE Set the encoding protocol to H.265. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 176 ECC800 Data Center Controller User Manual 6 Feature Description Figure 6-29 Setting primary stream parameters Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 177 ECC800 Data Center Controller User Manual 6 Feature Description Figure 6-30 Setting secondary stream 1 parameters ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 178: Commissioning A C3220 Camera (Sd Card Configured)

    If the VCN or IVS1800 is not configured and an SD card is chosen, perform the following procedure. Procedure Step 1 Log in to the Huawei camera WebUI. Step 2 Format the SD card. Choose Settings > System Configuration > Storage Management.
  • Page 179 ECC800 Data Center Controller User Manual 6 Feature Description Figure 6-31 Setting audio and video parameters NO TE If longer-time video storage is required, set camera parameters according to the following table. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 180 Add, add motion detection areas, set motion detection parameters, and click Save. Step 5 Set the deployment policy. Figure 6-32 Setting the deployment policy Step 6 Set the alarm linkage policy. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 181: Commissioning A Camera (Lan Switch Networking Scenario)

    – Google Chrome 45 or later versions need to install the Internet Explorer tab plug- – Only 32-bit web browsers are supported. Enter the preset user name admin and the preset password HuaWei123, and click Log In. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 182 1. Choose Tools > Internet Options. The Internet Options dialog box is displayed. 2. Click the Advanced tab. 3. Select Use TLS 1.1 or Use TLS 1.2. 4. Click OK. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 183 Choose Settings > Video/Audio/Image > Video, and set camera stream type, primary stream, and secondary stream 1 parameters, as shown in the following figures. NO TICE Set the encoding protocol to H.265. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 184 ECC800 Data Center Controller User Manual 6 Feature Description Figure 6-34 Setting primary stream parameters Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 185 ECC800 Data Center Controller User Manual 6 Feature Description Figure 6-35 Setting secondary stream 1 parameters ----End Follow-up Procedure Commission the other cameras by referring to this section. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 186: Commissioning An Ipc6325 Camera (Sd Card Configured)

    If the VCN or IVS1800 is not configured and an SD card is chosen, perform the following procedure. Procedure Step 1 Log in to the Huawei IPC WebUI. Configure the PC IP address and the camera IP address in the same network segment. Enter the camera IP address (192.168.0.120 by default) in the address bar of the Internet Explorer and press Enter.
  • Page 187 Duration H.265 1080P H.264 1080P H.265 720P 0.8M H.264 720P H.265 720P 0.6M H.264 720P 0.8M Select Enable, click Add, add motion detection areas, set motion detection parameters, and click Save. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 188 6 Feature Description Figure 6-38 Setting motion detection parameters Set the deployment policy. Figure 6-39 Setting the deployment policy Set the alarm linkage policy. Figure 6-40 Setting the alarm linkage policy ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 189: Commissioning A C3220 Camera

    Change Password to change the administrator password. – You need to set Internet Explorer before accessing the camera WebUI for the first time. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 190 WebUI cannot be opened. 1. Choose Tools > Internet Options. The Internet Options dialog box is displayed. 2. Click the Advanced tab. 3. Select Use TLS 1.1 or Use TLS 1.2. 4. Click OK. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 191 Preview the site situation in real time and check the camera coverage through videos. Adjust the lens if necessary. On the View tab page, click the Network/Time tab to access the Network/ Time tab page. Figure 6-41 Setting the IP address Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 192 Secondary DNS IP address. The default value is 0.0.0.0. On the View tab page, click the General tab to access the General tab page. Select Video and set the parameters, as shown in the following figures. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 193 ECC800 Data Center Controller User Manual 6 Feature Description Figure 6-42 Setting primary stream parameters Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 194 – Secondary stream: The secondary streams provide smooth video, occupy small bandwidth, and are applicable to data transmission over low-bandwidth networks. NOTE SD card recording supports only primary streams. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 195 Resolution A higher resolution indicates clearer images and higher bandwidth consumption. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 196 An I frame is an intra-coded frame that represents a fixed image independent of other picture types. Each group of pictures (GOP) begins with this type of frame. A smaller I-frame interval indicates better video quality and higher bandwidth consumption. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 197: Commissioning A C3220 Camera (Sd Card Configured)

    If the VCN or IVS1800 is not configured and an SD card is chosen, perform the following procedure. Procedure Step 1 Log in to the Huawei camera WebUI. Configure the PC IP address and the camera IP address in the same network segment. Enter the camera IP address (192.168.0.120 by default) in the address bar of the Internet Explorer and press Enter.
  • Page 198 Choose Settings > System Configuration > Storage Management. The Storage Management page is displayed. Format the SD card. Set the camera stream type and primary stream parameters. Path: Settings > Video/Audio/Image > Video Settings. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 199 ECC800 Data Center Controller User Manual 6 Feature Description Figure 6-45 Setting audio and video parameters NO TE If longer-time video storage is required, set camera parameters according to the following table. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 200 Choose Settings > Intelligent Analysis > Common Intelligence. Select Enable, click Add, add motion detection areas, set motion detection parameters, and click Save. Set the deployment policy. Figure 6-46 Setting the deployment policy Set the alarm linkage policy. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 201: Commissioning The Vcn

    Step 1 Log in to the OMU portal of the VCN. Step 2 Choose Local Configuration > Local Disk. Step 3 In the upper-right corner of the RAID Groups area, click Initial disk. Figure 6-48 Initializing disks Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 202 If RAID1 is selected for the disks, RAID 1 is created for both the system partition (used to store system data) and data partition (used to store recordings). Figure 6-49 RAID group status of RAID 1 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 203: Initializing Vcn520 Or Vcn540 Disks

    The function and configuration procedure of the VCN520 are the same as those of the VCN540. This section describes how to initialize VCN540 disks. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 204 RAID 5. Step 5 (Perform this step only when the RAID mode is set to RAID5.) Select RAID configuration. This step uses Recommended configuration as an example. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 205 Figure 6-54 RAID group status of disks that work independently (multiple disks) If only one disk is configured, RAID 0 is created for the system partition after disks are initialized. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 206: Setting Parameters On The Vcn Webui

    Enter the OMU Portal address (the default address for VCN500 is https://192.168.1.100:8443; the default address for VCN510&VCN520&VCN540 is https://192.168.2.101:8443) in the address bar of the Internet Explorer and press the Enter button. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 207 Search. In the search result, click Edit in the row where the value of Parameter Name is NatIP and set Value to the external IP address of the VCN. Click Save. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 208 Choose Maintenance > Unified Configuration. Select the server that the camera needs to access, set Module name to SCU and Parameter type to System property, and click Search. Figure 6-59 Configuring camera NTP synchronization Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 209: Setting Parameters On The Vcn Ivs Client

    OMU Portal system. ● (Optional) Set up a VCN stack. For details, log in to the https:// e.huawei.com/, search for the VCN product documentation, open the documentation, and see the section (Optional) Deploying IVS in Stack Mode.
  • Page 210 Method 2 1. Log in to the VCN OMU Portal, choose Local Configuration > Basic Configuration, and view Current version. 2. Log in to https://support.huawei.com/enterprise/, and search for Client Package.zip followed by the VCN model (Client Package.zip VCN540 for example). In the search result, click...
  • Page 211 Next. The Assign Rights page is displayed. NO TE When creating a user, you can select Enable account validity period and set Valid from and Valid to to set the account validity period for the created user. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 212: Commissioning The Ivs1800

    ● IP address: 192.168.3.111 ● Subnet mask: 255.255.255.0 ● Gateway address: 192.168.3.1 IP address :8443 in the address box, and press Enter. Step 2 Enter https:// Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 213 – RAID5 Economical Three or more hard disks are required, and one hard disk is used as the hot spare disk. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 214 Change the PC IP address to an address in the network segment of the new IVS1800 IP address, enter the IVS1800 IP address in the address box of the Internet browser, and log in to the OMU portal system. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 215 Value to the MUNNatIP address of the MU. Click Save. Figure 6-65 Setting the external IP address of the OMU (3) Configure the SMU: Set Module Name to SMU and click Search. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 216 The default TLS port number of the MU before mapping is 322. Step 7 (Optional) Configure the IVS1800 to synchronize time with the NTP server. Choose Local Configuration > Server configuration and configure the server time information. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 217 Click Save. After the camera NTP synchronization function is enabled, the camera, after being connected to the server, will automatically time- synchronize with the server. Figure 6-66 Configuring camera NTP synchronization Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 218: Setting Parameters On The Iclient

    Method 1 Obtain the iClient installation program from the OMU portal. Log in to the OMU portal, click Client Download in the upper right corner, and save the installation program to a local directory. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 219 Method 2 1. Log in to the OMU portal, choose Local Configuration > Basic Configuration, and view Current version. 2. Log in to https://support.huawei.com/enterprise/, choose Technical Support > Software Download > Intelligent Vision > Tools > iClient, select the version and patch number...
  • Page 220 "Reference Documentation" section. View the corresponding section. Choose System Management > Devices > Device Management > Micro Edge on the iClient home page. Right-click a device and choose Camera Access. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 221 ECC800 Data Center Controller User Manual 6 Feature Description Figure 6-70 Camera access Select Auto Batch Access and click Start. Search for cameras by IP address. Figure 6-71 Searching by IP address Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 222 Step 4 Configure a recording policy. Choose System Management > Devices > Device Management > Micro Edge on the iClient home page. Right-click a device and choose Storage Management. Figure 6-73 Selecting Storage Management Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 223: Linkage Control

    Edge on the iClient home page. Right-click a device and choose Storage Management. Click Server Recording Plan and configure a server recording plan. Figure 6-75 Server Recording Plan Click Save. ----End 6.6 Linkage Control Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 224: Fusionmodule2000 Linkage Control

    If this linkage status is set to on, with skylight open the skylights open automatically when a high temperature alarm is raised and all smart cooling products fail to communicate with the ECC800-Pro. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 225: Fire Control Linkage

    Refer to this section for details about opening the skylight, unlocking the aisle access control, and turning on the lighting system by fire linkage. ● In this example, the fire controller connects to port AI/DI_3. The actual port prevails. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 226 Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_3 Port Settings. Set Fire sensor to Enable. Click Submit to access the AI/DI_3 setting page. Select Fire sensor type and set it to Normal Open or Normal Close as required. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 227: High Temperature Linkage

    The default status of high temperature linkage is off. Set it based on the actual situation. Procedure Step 1 Log in to the ECC800-Pro WebUI as an administrator. Step 2 Choose System Settings > Linkage Control. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 228: Optional) Commissioning An Intelligent Aisle Light

    ● If you manually turn off the lighting when you leave the smart module, the lighting will be turned on again when the camera detects that the person leaves. ● The effective detection distance of the multi-functional sensor is 2.5 m. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 229 Table 6-40 Setting AC actuator parameters Path Operation Monitoring > Aisle > AC Actuator Set Route 1 Control Mode to Light, Group > AC Actuator > Running and click Submit. Parameters Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 230 Select the actual camera type and go to the camera web page. For details, see the section about camera commissioning. Choose Settings > Network > Platform Connection > Second Protocol Parameters. On the ONVIF and GENETEC tab pages, set platform interconnection parameters. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 231 Select Enable, click Add, add motion detection areas, set motion detection parameters, and click Save. Figure 6-79 Setting motion detection parameters If there are multiple cameras, repeat Step 8.1–Step 8.3. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 232: Linking The Smoke Alarm With Skylight Open

    Step 9 On the Linkage Group tab page, set Link smoke alarm with skylight open to Step 10 Add a logic program. NO TE If a skylight button is connected, perform this step. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 233 After Link smoke alarm with skylight open linkage is triggered and the alarm is cleared, perform the following operations: ● Press the reset button on the smoke sensor to clear the alarm. ● Close the skylight manually. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 234: High-Density Island Linkage

    Step 3 Go to the ECC running parameter page, click Unhide All Advanced Signals, and select Other Parameters. Set High-density island solution to Yes and click Submit. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 235 Confirm that Smoke sensor type is automatically identified as Smoke sensor or Smoke sensor(NC). Click Unhide All Advanced Signals, and click Power Supply Parameters. Ensure that III power supply enable(AIDI_1/DO) is Enable. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 236: Fusionmodule500/800 Linkage Control

    27°C, the emergency emergency fan starts. If all smart cooling products fail to provide the cooling function properly, and the aisle temperature is higher than 27°C, the emergency fan starts. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 237 NOTE If the fire extinguishing system is installed inside the smart module, the linkage function is not enabled. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 238: Link Air Conditioner Fault With Emergency Fan

    Set AI/DI_2 sensor to Enable. Click Submit to access the AI/DI_2 setting page. Select AI/DI_2 sensor type and set it to NTC. Click Unhide All Advanced Signals, then click Power Supply Parameters. Ensure that I power supply enable(AIDI_2/COM1/AIDI_4/COM3) is Enable. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 239: Link Smoke Alarm With Cabinet Electronic Clasp Lock Open

    6.6.2.3 Link Fire Control with Lock Open Context In this example, the fire controller connects to port AI/DI_2. The actual port prevails. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 240: Customizing Linkage Logic

    This function can be used when the default linkage logic does not fit the application scenario. ● This section describes how to add the logic for turning on lights when a door is opened. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 241 27°C and the hysteresis is 3" is configured, the air conditioner starts when the temperature is higher than 27°C and does not start when the temperature drops to 24°C. < Input 1 is smaller than input 2. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 242 Actuator Group- Turn On Lights Status Collection-Door Status Figure 6-84 Linkage logic diagram Step 6 Set Turn on lights if door open to on to make the linkage logic take effect. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 243: Infrared Remote Control Module Control And Management

    6.7.1 Connecting a Communications Cable Procedure Step 1 Connect the T/H sensor to the COM1 port on the ECC800-Pro using a network cable. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 244: Setting And Adding An Infrared Remote Control Module

    The address of the infrared remote control module is set to 2 by default. Step 2 Add the infrared remote control module. Log in to the ECC800-Pro WebUI as an administrator. Add an infrared remote control module and click Add Device. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 245: Control Function Of An Infrared Remote Control Module

    ● The infrared remote control module can be in infrared learning state and control code sending state. After power-on, the device is in normal operating mode by default. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 246 If the green indicator blinks, it indicates learning success of the first key code. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 247: Pue Configuration

    IT load output NOTE When the configuration mode is set to Standard, the ECC800-Pro can automatically calculate the PUE of multiple devices connected in the N+1 and 2N scenarios. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 248: Configuring Pue Standard Mode

    IT load output of the ECC800- Pro. Increment in total electrical energy of system IT load output = 56.0 kWh – 50.0 kWh = 6.0 kWh. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 249: Configuring Pue User-Defined Mode

    Total Power Consumption Configuration page. On the Select Device tab page, select Integrated PDU 1. On the Select Indicators tab page, select Total active electricity energy of PDU input, and click Confirm. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 250 Under Total Power Consumption Configuration and IT Cabinet Power Consumption Configuration, click the edit icon on the right to modify the multiple for calculating indicators, as shown in Figure 6-89. Figure 6-89 Editing a multiple Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 251: Viewing Pue

    – If the query time is between 18:00:00 and 19:00:00 and the time has not arrived at 19:00:00 yet, then the displayed time is 18:00:00 and the data includes the data from 18:00:00 to the query time. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 252: Battery Management

    Single battery Single battery capacity refers to the Obtain the battery capacity capacity of a single battery in a capacity from the battery string managed by the battery label or iBOX. document. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 253: Networking Iboxs And Ibats In Wireless Mode

    (iBattery 2.0) or short intervals (iBattery 3.0), and finally to blinking green at long intervals, the iBAT connects to the iBOX network. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 254: Battery Shallow Discharge Test

    Procedure Step 1 Log in to the ECC800-Pro WebUI as an administrator. Step 2 Choose System Settings > Linkage Control. Set Enable linkage control function to Yes and click Submit. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 255 Step 3 Set Battery shallow discharge test to On. Step 4 On the Linkage Logic List tab page, click Add or the edit icon Figure 6-92 Setting parameters for Linkage Logic List ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 256: Asset Management

    If a smart U space manager is installed, perform the following steps to configure Prerequisites Connect the smart U space manager to the COM1 or COM2 port on the rack environment unit. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 257: Querying The U Space Use Information

    6.10.2 Commissioning the Smart U Space Manager (Connected to a UIM20A Expansion Module) 6.10.2.1 Determining the Position of the Smart U Space Manager If a smart U space manager is installed, perform the following steps to configure Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 258: Querying The U Space Use Information

    Step 2 Choose Home > Plan View to access the Plan View page, where you can create or modify the views of the smart module. Drag the icon of a registered device or device in the cabinet list to the planned position to generate the plan view. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 259: Power Management

    Set power configuration parameters based on site requirements, such as the Device Name, Cabinet height, Power system, Number of power supplies, and Rated cabinet power. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 260 1QF2(L2), 2QF2(L2), and the like. ● Descending order: If the branch for the first cabinet is 1QF10(L1), 2QF10(L1), the branches for subsequent cabinets are 1QF9(L3), 2QF9(L3), and the like. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 261 The alarm hysteresis is 5% by default. That is, if the cabinet load factor overhigh alarm threshold is 90%, the raised alarm will be cleared when the load factor drops to a value smaller than 85%. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 262: Setting Fault Isolation Parameters

    Step 1 View the power information on the ECC800-Pro WebUI. Log in to the ECC800-Pro WebUI as an administrator. Choose Monitoring > Cabinet to access the Electricity Information in Each Cabinet page. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 263: Viewing The Power Supply Links Diagram

    Step 2 Log in to the ECC800-Pro app as the administrator. Step 3 View the power supply status of the smart module and basic information about each device in real time to quickly locate faults. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 264 ● Gray: The cabinet is not running. rPDU ● Yellow: smart rPDU (Click to view the rPDU number, current, and status) ● Blue or green: non-smart rPDU Branch switch SPD switch Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 265: Cooling Capacity Management

    ● All smart cooling products in the smart module need to be networked for teamwork. For details about how to configure teamwork networking, see the Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 266 Yes and click Submit to finish the iCooling function setting. Step 3 Set the iCooling temperature set point and humidity setpoint according to the actual environment. Figure 6-97 Setting the temperature and humidity setpoints Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 267: Viewing Cooling Capacity Usage Information

    When smart cooling products (NetCol5000-A025, NetCol5000-A042, and NetCol5000-A050) are connected to the ECC800-Pro, you can view the cooling link diagram. Procedure Step 1 Log in to the ECC800-Pro WebUI as an administrator. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 268 Air outlet temperature of the smart cooling product Return air temperature of the smart cooling product Smart cooling product status ● Blue: The smart cooling product is running. ● Gray: The smart cooling product is not running. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 269: Setting The Temperature Map

    Air outlet temperature of the smart cooling product ----End 6.12.4 Setting the Temperature Map If the temperature map function is configured, follow the instructions provided in this section to commission it. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 270 Set the T/H sensor device address through the DIP switch on the T/H sensor. Toggle switches 1–6 are used to set device addresses, toggle switch 7 is reserved, and toggle switch 8 is used to switch the temperature unit. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 271 Device to add the T/H sensor. The device connection information is displayed. Figure 6-103 Device connection Step 3 Bind the T/H sensor to the cabinet referring to 6.3 Commissioning a UIM20A Expansion Module. Step 4 Check functions of the T/H sensor. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 272: Facial Recognition

    The facial data is used only for configuring the facial recognition function and is not used for other purposes. The facial data is encrypted during transmission to ensure that the personal data of users is fully protected. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 273: Collecting And Importing Facial Data In Offline Mode

    On the login screen of the app, tap Settings and select Face Info Collection to collect facial data. In the Face Info Collection dialog box, set Please enter nickname and Please enter encryption password for the facial data, and tap OK. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 274: Opening The Access Control System Using Facial Recognition

    After facial recognition is successful, log in to the app as an administrator to open the access control system at the same time. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 275: Maintaining The Facial Data

    6.14.1 NetEco Management 6.14.1.1 Connecting a Communications Cable Networking Through the WAN1 Port Step 1 Connect the communications cable to the WAN1 port on the ECC800-Pro. Figure 6-105 Connecting a communications cable ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 276 Step 4 Insert the ECC800-Pro main control module into the slot. Step 5 Tighten the screws on both sides of the panel of the ECC800-Pro main control module. Step 6 Install a 4G antenna. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 277: Setting Neteco Parameters

    WAN_2 is administrator. involved Defaul – WAN_1: 192.168.8.1 Set this parameter in the based on the default FusionMo – WAN_2: 192.168.0.1 dule500/8 gatew gateway address assigned by the scenario. network administrator. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 278 Set this parameter to the IP address server IP of the backup NetEco server. NOTE This parameter is displayed when Enable standby server IP next to Server IP is selected. Port number 31220 31220 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 279: Creating An Ecc800-Pro On The Neteco

    ----End 6.14.1.3 Creating an ECC800-Pro on the NetEco Prerequisites ● You have logged in to the NetEco client using a web browser. ● You have created modules in Data Center Planning. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 280 Figure 6-109 Adding an ECC800-Pro device to the smart module NO TE Click OK, and you can view the task information, including Type, Device Name, Management Domain, Progress, Status, Start Time, End Time, and Detailed Information in the displayed window. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 281: Setting The Transparent Transmission Function

    If the port is set for the first time, you are prompted to set an authentication password. On the Set Authentication Password tab page, set Authentication password and Confirm authentication password and click Submit. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 282 Step 13 In the navigation tree on the left, choose Transparent Transmission Channel Management. Step 14 Click Modify after selecting the IP address of the ECC800-Pro connected to the NMS. Step 15 In the Modify dialog box, set Connection Mode. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 283: Third-Party Nms Management (Over Snmp)

    Step 1 Connect a communications cable to the WAN1 port on the ECC800-Pro. Figure 6-111 Connecting a communications cable ----End 6.14.2.2 Setting SNMP Management Parameters Prerequisites Before setting SNMP parameters, obtain the information listed as follows from the NMS. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 284 Settings > address assigned by the network System administrator. Parameter Subnet 255.255.25 Set this parameter based on the s > mask subnet mask assigned by the network Monitor IP administrator. > WAN_1 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 285: Setting Other Parameters And Channel Security

    Digital Power > Fusion Modular Data Center > ECC800, and decompress the software package to obtain the MIB file. For carrier users: Log in to https://support.huawei.com, download the software package of the required version from Support > Software > Digital Power > Data Center Facility >...
  • Page 286 Manually updating a The system provides the automatic key update function. Manual update is required only if the key is disclosed. Select the parameter and click Submit. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 287: Robot Management

    Use a network cable to connect the PC to the network port of the robot. Enter https://192.168.248.10 in the address box of the browser on the PC, and then press Enter to access the WebUI login page. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 288 – After the first login, change the password in time to improve account security and prevent unauthorized network attacks, such as data tampering. Huawei will not be liable for any loss caused by your failure to change the password in time or to keep the new password properly.
  • Page 289 WAN1 or WAN2 port. ● Click an operation icon for the corresponding SSID to modify, delete, or manually connect to the WiFi network. Figure 6-114 Selecting a hotspot Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 290 Step 4 Choose System Settings > NMS Application > NetEco, set Server IP and Port number, select WIFI for Network port for link setup, and click Submit. NO TE The default port number is 31220. Figure 6-116 Setting communications parameters Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 291 Controls the robot to return to the charging pile for charging. Robot IPC Robots the robot IPC. reboot Robot IPC Clears robot IPC alarms. alarm clear Fill light Turns on or off the illuminator on the PTZ camera. control Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 292: Intelligent Inspection

    Step 2 Choose System Settings > System Parameters > Site Configuration, set System type to General, and click Submit. Enter the login password of the current user and click Submit. After the system restarts, log in to the system again. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 293 Parameters > Unhide All Advanced Exhaust fan doorside sound model Signals Exhaust fan innerwall sound model Supply fan doorside sound model Supply fan innerwall sound model Water pump side sound model Other model Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 294: Numbering Management For Power Distribution Devices In The Power Module

    Power distribution devices have been connected to the ECC800-Pro. ● The power module plan view has been created, and the device positions in the plan view are consistent with actual positions. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 295 Step 3 Click Modify Device, double-click the corresponding power distribution device, and set Device No. based on the device number planned in the power supply and distribution link diagram. Figure 6-123 Setting the device No. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 296: Intelligent Networking Of Fusionmodule2000 Busways

    Step 1 Go to the FusionModule2000 view, click Modify Device, select any general input unit or power distribution unit, and click Automatic identification. NO TE You can set Power supply branch to manually change the link relationship. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 297 ECC800 Data Center Controller User Manual 6 Feature Description Figure 6-124 Networking settings ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 298: Maintenance

    –20°C to +50°C abnormal, check the smart cooling product status. ● Humidity: 0-95% RH (non-condensing) Cable The cable connection is Secure loose cables. connection secure. Cables are not damaged. Replace damaged cables. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 299: Common Faults And Troubleshooting

    Check whether the AC undervoltage protection input is abnormal. is triggered. The ALM indicator Communication with the 1. Clean the connector (yellow) is blinking. PSU is interrupted. in the rear of the faulty PSU. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 300 If yes, eliminate the short circuit. The ALM indicator (red) is An alarm is generated. View active alarms on steady on. the WebUI and clear them one by one. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 301 AI_DI unit and the AI_DI unit is faulty and ECC800-Pro is abnormal, whether the cable or the independent connection between the deployment AI_DI unit is ECC800-Pro and faulty. independent deployment AI_DI unit is normal. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 302: Component Replacement

    Tools: ESD wrist strap, ESD gloves, Phillips screwdriver, labels, marker ● Materials: a new undamaged and undeformed ECC800-Pro main control module of the appropriate model Procedure Step 1 Log in to the ECC800-Pro WebUI as an administrator. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 303 Step 6 (Optional) Remove the SIM card from the corresponding slots of the ECC800-Pro main control module. Step 7 (Optional) Install the removed SIM card in the corresponding slot of the new ECC800-Pro main control module. Figure 7-2 Installing a SIM card Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 304: Replacing An Ecc800-Pro Psu

    Step 2 Pull out the handle of the PSU to remove the PSU from the subrack. Step 3 Gently push the reserved PSU into the subrack along guide rails, and push the locking latch rightwards to secure the handle. Figure 7-3 Replacing a PSU ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 305: Replacing Ecc800-Pro Antennas

    Step 2 Loosen the screws on both sides of the ECC800-Pro main control module. Step 3 Pull the handles on both sides of the ECC800-Pro main control module, and to remove the main control module. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 306 Step 7 Tighten the screws on both sides of the ECC800-Pro main control module. Step 8 Reconnect signal cables to the ECC800-Pro main control module panel based on the recorded information. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 307: Faq

    Step 1 Go to the WebUI login page. Enter the user name and password to log in to the ECC800-Pro home page. Step 2 Download the .zip upgrade package from the Huawei enterprise or carrier website. After the decompression, choose Maintenance > System Upgrade on the ECC800-Pro WebUI, click Select File, and select the decompressed .tar.gz file...
  • Page 308: How Can I Set The Date And Time

    SMS. After Smart module name is changed, the new site ID will be displayed in the short message content (for example, XXX device communication interruption) Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 309: How Can I Manage Webui Users

    ● Operator: The user name is operator and password is Changeme by default. Operator has no rights for user management, system setting, version upgrade, Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 310 Figure 8-2 Changing the login password Modify Advance expiration notification (days) and Timeout Interval for the password. Determine whether to enable multi-factor authentication based on user requirements. Select the notification mode. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 311 Specify User name, Password, Confirm password, Password validity period, Advance expiration notification (days), and Timeout Interval, select appropriate values from the Access right and Login source drop-down list boxes, and click Confirm. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 312 If you forgot the password, perform the following steps: Click Forgot password. Figure 8-4 Clicking Forgot password Specify the user name. Enter the verification code. Figure 8-5 Retrieving a password Click Next to retrieve the password. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 313: How Do I Create A Smart Module Plan View

    If both room-level and smart module access actuators exist, modify the value of Device Name to distinguish them. The value of Device Name for the power distribution unit should be consistent with its label, for example, NMW A 01. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 314 Exit Edit Mode. The smart module plan view is updated. When editing the smart module view, click Zoom In or Restore to adjust the size of the view. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 315: How Can I Set And Add Devices

    COM_2 port on the Modbus expansion card of the UPS2000G-A, and the other end has been connected to the COM port on the ETH converter. Procedure Step 1 Set monitoring parameters for the UPS2000G-A. ● Set monitoring parameters for UPS2000G-A-(1 kVA–3 kVA). Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 316 Log in to the ECC800-Pro WebUI as an administrator. Add a UPS2000G-A. Table 8-3 Adding a UPS2000G-A Path Parameter Setting Choose Device Select UPS from the drop-down list box. System attribute Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 317: How Can I Set And Add A Ups2000G_L (Modbus-Rtu)

    COM port on the ECC800-Pro or ETH converter. Procedure Step 1 Set the communications address parameters for the UPS2000G_L. NO TE UPS2000-G-6KRTLL User Manual . For details, see the Step 2 Add a UPS2000G_L. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 318: How Can I Set And Add A Ups5000 (Modbus-Rtu)

    If all devices have been added and powered on, only the BLINK function of the ETH converter can be used to identify the mapping between the UPS5000 and ETH converter. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 319 Choose Monitoring > System > ETH Converter Group > ETH Converter n > Running Parameters and set Device name to ETH Converter n_Device name. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 320: How Can I Set And Add A Ups5000 (Modbus-Tcp)

    000001, and tap Tap Communication to set IP address assign to Automatic(DHCP) on the displayed communication settings screen and the PDU8000 is discovered by ECC800-Pro automatically and is connected to the ECC800-Pro. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 321: How Can I Set And Add A Transformer (Modbus-Rtu)

    The temperature controller exits the communication address setting state and returns to the temperature display state. Step 2 Add a transformer. Log in to the ECC800-Pro WebUI as an administrator. Add a transformer. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 322: How Can I Set And Add An Svg-In-Power (Modbus-Rtu)

    Tap Expert Setting. On the displayed SVG communication settings screen, set ID to 1 and Baud to 9600. NO TE ID is the communication address, ranging from 1 to 255. This operation uses 1 as an example. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 323 If the connection fails, check whether the device is properly connected to the ECC800-Pro, whether the device and ECC800-Pro are running properly, and whether the parameter settings are consistent with the device parameters. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 324: How Can I Set And Add An Envicool Air Conditioner (Modbus-Rtu)

    Add Connect To Select ECC800 from the drop-down list Device. box. NOTE If the other end of the straight-through cable is connected to the COM port on the UIM20A, select UIM. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 325 If the connection succeeds, click Confirm. The connected devices are displayed in the Number of connected devices list. – If the connection fails, check whether the device is properly connected to the ECC800-Pro, whether the device and ECC800-Pro are running Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 326: How Can I Set And Add A Dc Pdf (Modbus-Rtu)

    Click Test Connect to check whether the DC PDF is properly connected to the ECC800-Pro. – If the connection succeeds, click Confirm. The connected devices are displayed in the Number of connected devices list. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 327: How Can I Set And Add A Smartli (Modbus-Tcp)

    ETH gateway. Procedure Step 1 Log in to the ECC800-Pro WebUI as an administrator. Step 2 Open the aisle door. NO TE The following describes how to remotely open a door. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 328: How Can I Set And Add A Pdu8000 (Modbus Rtu)? (C41)

    Confirm. Tap Communication to access the PDU8000 communication settings screen and set IP address assign to Manual. Set Serial port baud rate to 9600, and Serial port address to 1. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 329 Click Test Connect to check whether the PDU8000 is properly connected to the ECC800-Pro. – If the connection succeeds, click Confirm. The connected devices are displayed in the Number of connected devices list. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 330: How Can I Set And Add A Dc Power Supply (Modbus-Rtu)

    Select MTS9604B_MTS9606B Power Device Supply from the drop-down list box. Management and click Add Connect To Select ECC800 from the drop-down list Device. The box. parameters for adding devices are displayed. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 331: How Can I Set And Add An Rpdu

    Table 8-14 rPDU basic information Model Vendor Name Displayed Eleventh and on the WebUI Twelfth Characters in Device Barcode PDU2000-32-1PH Clever PDU2000-M(C) -20/4-M1/CLEVER PDU2000-32-1PH HPXIN PDU2000-M(H) -20/4-M1/HPX MD-1324-2004 Clever rPDU-MPDU PN1-32I10-20E4G HPXIN rPDU-PN -AV4 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 332 Figure 8-11 PDU2000-M (C) initialization screen – Press MENU to enter the device communications address screen. Figure 8-12 PDU2000-M (C) communications settings – Press the DOWN and UP buttons to select the address to be set. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 333 Select PDU from the drop-down list box. System attribute Settings > Device Type Select PDU2000-M (C) or PDU2000-M Device (H) from the drop-down list box based on Management the actual device. and click Add Device. The Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 334: How Can I Set And Add An Ats

    ● The ATS device address is 1 by default. ● The initial password is 0001 for the ATS display panel. Step 2 Add an ATS. Log in to the ECC800-Pro WebUI as an administrator. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 335: How Do I Set And Add An Electricity Meter

    COM port on the ECC, UIM, or ETH converter that connects to the electricity meter to ensure that the parameters are consistent with the communications parameters of the electricity meter. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 336 The supported electricity meter models are subject to change due to product upgrade. The actual UI may vary. Figure 8-14 Electricity meter models Procedure Step 1 Log in to the ECC800-Pro WebUI as an administrator. Step 2 Add an electricity meter. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 337: How Can I Set And Add A Netcol5000-A011/A025/A035/A042/A050/A065 (Modbus-Tcp)

    000001. After login, the settings screen of the NetCol5000-A042 is displayed. Choose Comm Settings > LAN IP Settings, set LAN IP assigning mode to Automatic (DHCP), and click Submit. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 338: How Can I Set And Add A Netcol5000-A025 (Modbus-Mac)

    Choose Comm Settings > LAN IP Settings, set LAN IP assigning mode to Automatic (DHCP), and click Submit. Choose Settings > Comm Settings > Modbus Settings, and set Connection mode to Server and client, Server encryption to Enable. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 339: How Can I Set And Add A Netcol5000-C(030, 032)/Netcol5000-C(065, 080) Parameters (Over Modbus Tcp)

    Choose Settings > Comm Settings > LAN IP Settings, set LAN IP assigning mode to Automatic(DHCP), and tap Submit. Choose Settings > Comm Settings > Modbus Settings, and set Connection mode to Server and client, Server encryption to Enable. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 340: How Can I Set And Add A Netcol5000-C030 (Modbus Rtu)

    Choose Settings > Comm Settings > Modbus Settings, choose Baud rate to 9600 and set Comm address to 1. NO TE The earlier version has Protocol setting on the screen. The actual screen prevails. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 341 The displayed value prevails. On the Running Parameters tab page, set smart cooling product running parameters. On the Controls tab page, set the smart cooling product control parameters (such as on/off control parameters). Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 342: How Can I Set Netcol8000-A Parameters (Modbus-Tcp)

    The displayed value may vary. On the Running Parameters tab page, set smart cooling product running parameters. On the Controls tab page, set the smart cooling product control parameters (such as on/off control parameters). Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 343: How Can I Set And Add An Ip Device

    Step 5 Click Submit. The IP Device 1-5 tab page is displayed. Step 6 On the IP Device 1-5 tab page, set Enable online detection IP device 1 to Enable. Step 7 Click Submit. Step 8 Specify IP device 1 address. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 344: How Can I Set And Add An Independent Deployment Ai_Di Unit

    The device address for the independent deployment AI_DI unit can only be set to 1 or 2. Table 8-19 Setting a device address Address Toggle Switch 1 Toggle Switch 2 Toggle Switch 3 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 345 ECC800-Pro, whether the independent deployment AI_DI unit and ECC800-Pro are running properly, and whether the parameter settings are consistent with the independent deployment AI_DI unit parameters. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 346: How Can I Set And Add A Uim20A Expansion Module (Modbus-Tcp)

    On the WebUI, choose Monitoring > Aisle > Multi-Func Sensor Group > Multi- Func Sensor1 > Running Parameters, ensure that Smoke enable and Temp enable are set to Enable, set High temperature alarm threshold and other parameters as required, and then click Submit. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 347 ● After the commissioning is complete, clean up dust. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 348: How Can I Set And Add The Smoke Sensor (Connected To The Ai/Di Port On The Ecc800-Pro)

    Core wire 1 (orange-white), core GND (black) wire 8 (brown) Core wire 3 (green-white) +12 V (red) Core wire 6 (green) Normally closed end (yellow) Core wire 7 (brown-white) Common end (green) Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 349 Confirm that Smoke sensor type is automatically identified as Smoke sensor or Smoke sensor(NC). Click Unhide All Advanced Signals, then click Power Supply Parameters. Ensure that I power supply enable(AIDI_2/COM1/AIDI_4/COM3) is Enable. Step 2 Check the monitoring functions of smoke sensor. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 350: How Can I Set And Add The Smoke Sensor (Connected To The Ai/Di Port On The Skylight Actuator)

    Core wire 7 (brown-white) Common end (green) None (reserved; no connection needed Normally open end (blue) and to be insulated) Context ● If the sensor is prefabricated, only check its settings. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 351: How Can I Set And Add The Smoke Sensor (Connected To The Ai/Di Port On The Rack Environment Unit)

    AI/DI port on the rack environment unit. Context ● If the sensor is prefabricated, only check its settings. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 352: How Can I Set And Add The Smoke Sensor (Connected To The Ai/Di Port On The Uim20A Expansion Module)

    AI/DI port on the UIM20A expansion module. Context ● If the sensor is prefabricated, only check its settings. ● The actual value prevails. Only the method of the parameter settings is described. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 353: How Can I Set And Add The Wlds900 Water Sensor

    ● If the sensor is prefabricated, only check its settings. ● The actual value prevails. Only the method of the parameter settings is described. Procedure Step 1 Set water sensor parameters. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 354: How Can I Set And Add A Wlds600 Water Sensor

    COM port on the ECC800-Pro. Procedure Step 1 The default communications address 1 of the water sensor is used for connecting to the ECC800-Pro. Step 2 Log in to the ECC800-Pro WebUI as an administrator. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 355 Log in to the ECC800-Pro WebUI as an administrator. Choose Monitoring > System > Water Sensor > Running Parameters. Set the parameters based on actual conditions, and click Submit. Step 6 Check functions of water sensors. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 356: How Can I Set And Add An Electrode Water Sensor

    Set Device type to ECC800, set Device name to ECC800, and click OK. On the query result tab page, set the new signal name of AI/DI_5 to Leak and click Submit. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 357: How Can I Set And Add The Temperature Sensor (Connected To The Ai/Di Port On The Ecc800-Pro)

    In this example, the temperature sensor is connected to the AI/DI_2 port on the ECC800- Pro. Log in to the ECC800-Pro WebUI as an administrator. Choose System Settings > Signal Name Modify. The Batch Signal Configuration page is displayed. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 358: How Can I Set And Add The Temperature Sensor (Connected To The Ntc Port On The Rack Environment Unit)

    Step 2 Check the monitoring functions of the temperature sensor. Table 8-33 Function check Check Method Normal Connection Status Path: Monitoring > Cabinet You can view the current cabinet temperature. > IT Cabinet n > Cabinet Collector n Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 359: How Can I Commission A Temperature Sensor (Connected To The Ntc Port On The T/H Sensor)

    Log in to the ECC800-Pro WebUI as an administrator. Add the T/H sensor. Choose System Settings > Device Management and click Auto Discover Device to add the T/H sensor. The device connection information is displayed. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 360: How Can I Set And Add A T/H Sensor (Bom Number: 33010516)

    ON indicates 1, and OFF indicates 0. Table 8-35 Setting a device address Address Toggle Toggle Toggle Toggle Toggle Toggle Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Switch 6 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 361 Choose Monitoring > Aisle > T/H Sensor Group information about the T/H > T/H Sensorn > Running Info, and check the sensor on the WebUI. current T/H information of the cabinet. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 362: How Can I Set And Add The T/H Sensor (Bom Number: 02310Nbs)

    ON indicates 1, and OFF indicates 0. Table 8-38 Setting a device address Address Toggle Toggle Toggle Toggle Toggle Toggle Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Switch 6 Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 363 Choose Monitoring > Aisle > T/H Sensor Group information about the T/H > T/H Sensorn > Running Info, and check the sensor on the WebUI. current T/H information of the cabinet. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 364: How Can I Set And Add A T/H Sensor (Bom Number: 02311Fqg/02312Pbl)

    Device addresses are set in binary encoding format in the range of 1–63. The first bit is the least significant bit, and the sixth bit is the most significant bit. ON indicates 1, and OFF indicates 0. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 365 If the connection fails, check whether the T/H sensor is properly connected to the ECC800-Pro, whether the T/H sensor and ECC800-Pro are running properly, and whether the parameter settings are consistent with the T/H sensor parameters. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 366: How Can I Add An Smu11B

    192.168.0.11, subnet mask to 255.255.255.0, and default gateway to 192.168.0.1 on the PC. Step 2 Enter https://SMU IP address (for example, https://192.168.0.10) in the address box of the browser, and then press Enter to access the WebUI login page. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 367 Step 3 Choose System Settings > Serial Port and set Communication Address as planned. Figure 8-20 Setting the communications address Step 4 Add an SMU11B. Log in to the ECC800-Pro WebUI as an administrator. Add a device. Figure 8-21 Adding a device Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 368: How Can I Restore Factory Settings

    Step 3 Enter the password currently used for logging in to the WebUI and click Submit. ----End 8.9 How Can I Install a Network Security Certificate? Context ● You have copied a network security certificate and its key you obtained to the Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 369: How Can I Install A Device Access Certificate

    Procedure Step 1 Log in to the ECC800-Pro WebUI as an administrator. Step 2 Choose System Settings > Device Management > Security Certificate Change. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 370: How Can I Change The Ecc800-Pro Ip Address On The Webui

    You can set Severity to Critical, Major, Minor, or Warning as required. – After an alarm and a DO output are associated over Output Dry Contact, the device connected to the DO port will act if the alarm is generated. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 371: How Can I View Real-Time Monitoring Data, Active Alarms, Historical Alarms, Access Event, And Operation Logs

    Step 3 Choose Home > Active Alarms to view the active alarms of the ECC800-Pro. Click Details in the Alarm Details area to view alarm details of devices. Step 4 Choose Query to view the historical alarms, access events, and operation logs of the device. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 372: How Can I Handle Alarms

    In this example, the smoke sensor is connected to the AI/DI_3 port on the ECC800-Pro. ● The following procedure describes how to change the signal name of AI/DI_3. Other signal names can be changed in a similar way. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 373: How Can I Export Historical Data And Device Data

    Record the password for decompressing the data package. Step 4 Export historical data and local data of southbound devices, and select a save path to save the exported data to the PC. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 374: How Can I Export Or Import A Configuration File

    Procedure Step 1 Log in to the ECC800-Pro_1 WebUI as an administrator. Step 2 Choose Maintenance > Configuration File. Step 3 Export a configuration file. Specify Configuration file encryption password. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 375: How Can I Export Fault Information

    To ensure data security, you are advised to select Encryption password. NO TE Record the password for decompressing the data package. Step 4 Export fault information and save the exported data to the PC or USB flash drive. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 376: How Can I Synchronize Device Parameters

    NO TICE If communication between the ECC800-Pro and the device is interrupted during parameter synchronization, the synchronization fails. Ensure that the ECC800-Pro and the device communicate properly and synchronize parameters again. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 377: What Should I Do If The Ecc800-Pro Webui Display Language Changes From Chinese To English During Use

    Step 1 If the ECC800 has been connected to the NMS, you can query the IP address on the NMS. Step 2 If the ECC800 is not connected to the NMS, hold down the SW button on the ECC800 for 1 minute to restore the default IP address. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 378: What Should I Do If A Message Indicating Unauthorized Fingerprint Is Displayed During Fingerprint Scanning On The Access Control Device (Fingerprint Has Been Recorded)

    Step 3 If the message indicating unauthorized fingerprint is still displayed after you perform Step 1 Step 2, you need to record the user's fingerprint again. Choose System Settings > Access Management. Select the involved user and record the fingerprint again. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 379: How Can I Rectify Camera Access Restriction

    8 FAQ 8.25 How Can I Rectify Camera Access Restriction? Prerequisites If Huawei S12700 series switch is used, refer to this section to rectify the fault. For more information, consult network engineers. Context The camera is inaccessible after the MAC address and IP address are bound in network configuration.
  • Page 380 Follow-up Procedure Choose Home > Plan View on the ECC800-Pro WebUI, and drag the device to the corresponding position in the Smart Module View pane based on the actual device layout. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 381: How Can I Add The Devices Accessed Through A Smart Eth Gateway To The Ecc800-Pro Webui (Modbus-Mac)

    The following is an example of confirming the access of a WiFi converter. ● If the device exists, and communication status is normal, the device has accessed the ECC800-Pro successfully. Figure 8-29 Device accessed the ECC800-Pro Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 382: How Can I Add Devices Accessed Through The Eth Converter To The Ecc800-Pro Webui

    8.28 How Can I Add Devices Accessed Through the ETH Converter to the ECC800-Pro WebUI? Context Figure 8-30 Networking scenario Procedure Step 1 Set communications parameters on the device. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 383 If the connection fails, check whether the device is properly connected to the ECC800-Pro, whether the device and ECC800-Pro are running properly, and whether the parameter settings are consistent with the device parameters. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 384: How Can I Add Devices Accessed Through The Ecc800-Pro Com Port To The Ecc800-Pro Webui

    Parameter Recommended Value Baud rate This section uses 9600 as an example. Set this parameter based on site requirements. NOTE For certain devices, this parameter does not need to be set. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 385 Follow-up Procedure Choose Home > Plan View on the ECC800-Pro WebUI, and drag the device to the corresponding position in the Smart Module View pane based on the actual device layout. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 386: How Can I Add Devices Accessed Through The Ecc800-Pro Ai/Di Port To The Ecc800-Pro Webui

    Table 8-47 Parameter description for adding a device Path Parameter Setting Monitoring > AI/DI_3 Select Enable and click Submit System > ECC800 sensor > Running Parameters > AI/ DI_3 Port Settings Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 387: How Can I Add An Rs485 Device Connected To The Ecc800-Pro Through A Uim20A

    This section uses the device (such as a T/H sensor, rPDU, cabinet electronic lock, and U-bit manager) connecting to the COM1 port on the UIM20A expansion module as an example. Procedure Step 1 Set communications parameters on the device. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 388: How Can I Add A Dry Contact Device Connected To The Ecc800-Pro Through A Uim20A Expansion Module

    In the scenario with multiple UIMs in the same smart module, a maximum of 48 dry contact devices can be connected. Procedure Step 1 Log in to the ECC800-Pro WebUI as an administrator. Step 2 Add the device. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 389: How Can I Open Doors Remotely Over The Ecc800-Pro Webui

    Context If O&M personnel need to enter a smart module but do not take an access cord or forget the password, you can open the door remotely over the ECC800-Pro WebUI. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 390: How Can I Turn On Or Off Aisle Lights In The Smart Module Over The Ecc800-Pro Webui

    ECC800-Pro WebUI. ● When the local light button is faulty or lights cannot be turned on through a linkage, you can remotely turn on the lights over the ECC800-Pro WebUI. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 391 Follow-up Procedure Set Set light mode to Automatic. CA UTION When a smart module actuator is configured, you need to set parameters for the smart module actuator. The setting process is similar. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 392: How Can I Open Skylights Remotely Over The Ecc800-Pro Webui

    ● When a smart module actuator is configured, you need to set parameters for the smart module actuator. The setting process is similar. ----End Example The following figure shows how to open the skylights controlled by skylight actuator 1. Figure 8-36 Opening skylights Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 393: How Can I Turn On Or Off Smart Cooling Products Over The Ecc800-Pro Webui

    NetCol n > Controls required, and click Submit. ----End Example The following figure shows how to turn on or off the NetCol5000-A025. Figure 8-37 Turning on or off smart cooling products Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 394: How Can I Open The Cabinet Electronic Lock Over The Ecc800-Pro Webui

    The following figure shows how to open electronic lock 1 for IT cabinet 1. Figure 8-38 Opening a cabinet electronic lock Follow-up Procedure After the maintenance is complete, O&M personnel need to close the cabinet door manually. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 395: How Can I Link The Smoke Alarm With The Alarm Beacon Over The Ecc800-Pro Webui

    This section describes how to set an alarm linkage by linking output dry contact of the smoke DI alarm on the AI/DI_1 sensor to the DO port. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 396: How Can I Modify Device Names Over The Ecc800-Pro Webui

    Select Device name, enter the new name in the Smart ETH Gateway text box as planned, and click Submit. Group > Smart ETH Gateway 1 > Running Parameters ----End 8.41 How Can I Perform Operations on the App? Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 397: How Can I Connect To A Wifi Network

    ● Huawei AppGallery installed on the PAD Log in to the Huawei AppGallery client, search for FusionModule, and tap Install. Huawei AppGallery is preinstalled on Huawei PAD by default. ● Huawei AppGallery not installed on the PAD Issue 04 (2021-10-09) Copyright ©...
  • Page 398 ECC800 Data Center Controller User Manual 8 FAQ Table 8-56 Operation methods for the scenario where Huawei AppGallery is not installed on the PAD Method Procedure Installation Verification Method 1: Install the 1. Log in to Huawei Check that the app icon...
  • Page 399 IP address is 192.168.245.10. The user name and login password for the app are the same as those for the ECC800-Pro WebUI. Specify the user name and password, and tap Login. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 400: How Can I Ensure That Device Positions In The Plan View Are Consistent With Actual Positions

    Check that the device positions and types in the plan view are consistent with the actual situation by delivering the blinking command. Figure 8-40 Rack environment unit blinking ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 401: How Can I View Real-Time Data

    The configuration file is encrypted, enter the password in the Decryption Password text box. Select a configuration file and tap Import. NO TE The ECC800-Pro will restart after you import the configuration file. ----End 8.41.6 How Can I Synchronize Device Parameters? Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 402: How Can I Handle App Login Failure

    Step 2 If you have not obtained the user name and password used in a previous successful login, perform the following operations: Close the app and wait for about 22 to 23 minutes. Log in as the current user. ----End Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 403: Plc Function

    FILTER: The output is active if the input reaches the constant. ● Outputs: – Outputs are associated with dry contact outputs and can be used for generating alarms or controlling devices. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 404: Linkage Control Configuration Examples

    The following describes how to configure the linkage control linkage, using Link fire control with skylight open as an example. ● In this example, the fire controller connects to port AI/DI_1. The actual port may vary. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 405 Opening the skylights may cause the cooling effect to fail. Figure 9-2 Parameters for connecting to the temperature sensor Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 406 You can use the configuration file import and export function to export the linkage control linkage rules configured for an ECC800-Pro to a local PC and then import the rules to another ECC800-Pro. This function achieves quick configuration for the linkage control. Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 407: Acronyms And Abbreviations

    Advanced encryption standard analog input application battery control I/O board component object model direct current Data Encryption Standard digital input digital output Energy Control Center equipment serial number Ethernet Fast Ethernet Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 408 NetEco iManager NetEco data center infrastructure management system negative temperature coefficient power distribution unit power over Ethernet power supply unit power usage effectiveness radio frequency relative humidity Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.
  • Page 409 Simple Mail Transfer Protocol SNMP Simple Network Management Protocol Secure Sockets Layer SSID service set identifier Transport Layer Security uninterruptible power system universal serial bus video cloud node WiFi wireless fidelity WiFi protected setup Issue 04 (2021-10-09) Copyright © Huawei Technologies Co., Ltd.