Huawei FusionModule2000-S User Manual page 136

Smart modular data center
Hide thumbs Also See for FusionModule2000-S:
Table of Contents

Advertisement

FusionModule2000-S Smart Modular Data Center
User Manual
Figure 5-2 Standard BSC mode
Step 2 Set the master BSC system. On the LCD of a UPS, choose System Info > Settings
> System Settings and set BSC master/slave system to BSC master system.
Figure 5-3 BSC master system
Step 3 Set the slave BSC system. On the LCD of the other UPS, choose System Info >
Settings > System Settings and set BSC master/slave system to BSC slave
system.
Figure 5-4 BSC slave system
Step 4 If no alarm is generated after settings, the UPS runs properly.
----End
Issue 03 (2021-07-15)
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
127

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r021c10

Table of Contents