Determining The Faulty Area And Alarm Severity - Huawei IDS1000-A Maintenance Manual

Air-cooled container data center
Table of Contents

Advertisement

IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
Procedure
Step 1 Enter your user name and password to log in to the NetEco.
Step 2 Choose Fault > Current Alarms, and view the current alarm information.
Step 3 Collect alarm information.
----End
Example
Table 4-1
Table 4-1 Alarm information collection table
Alarm
Time

4.3 Determining the Faulty Area and Alarm Severity

After receiving a fault alarm, determine the alarm severity immediately. If the alarm is critical,
troubleshoot by following instructions in
locate and handle the alarm by following instructions in
Issue 01 (2016-01-10)
If the password was changed when the management system was commissioned, enter the
new password.
If the password was not changed when the management system was commissioned, enter
the initial password.
After an alarm is generated, immediately collect the following information:
Occurrence time and place
Detailed fault symptoms
Operations performed before the fault occurs
Services and scope affected by the fault alarm
Measures taken after the fault occurs and the effect
describes an alarm information collection template.
Alarm
Location
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Sympto
Type
m
6 Emergency
4 Alarms and Faults
Current
Impact
Operatio
n
Operations. If the alarm is not critical,
4 Alarms and
Faults.
Measures
Taken and
Effect
47