FusionModule2000-S Smart Modular Data Center
User Manual
Maintenance
Item
Wet film
humidifier
Table 6-7 Quarterly maintenance for the management system
Maintenance
Item
Battery
management
parameter
settings
Fire control
linkage function
Issue 03 (2021-07-15)
Method
Start the
equipment,
choose Maint
> Diagnostic
Mode > Enter
on the main
screen, and
start the wet
film
humidifier.
Method
On the UPS
LCD, choose
System Info >
Settings >
Battery
Param. and
check whether
battery
management
parameters
are set as
required.
Simulate a
smoky
environment
under the
smoke
detector. (If
real smoke is
not allowed,
press the TEST
button on the
sensor.)
Copyright © Huawei Technologies Co., Ltd.
6 Operation and Maintenance
Expected Result
Water drainage is
normal.
Expected Result
The parameters are
set based on
requirements.
A smoke alarm is
displayed on the
active alarm page of
the WebUI.
Troubleshooting
● If no water is
supplied, check
the cable
connection or
replace the water
inlet solenoid
valve.
● If no water is
supplied to the
wet film
humidifier, check
the cable
connection to the
water pump or
replace the
humidifier water
pump.
Troubleshooting
Set parameters
correctly.
Check whether the
smoke detector is
faulty.