5.3 Power-On Commissioning for the Management
System

5.3.1 Preparations and WebUI Login

Prerequisites
Procedure
Step 1 Connect the PC network port and the WAN1 port (protected by a security
mechanism) on the ECC800-Pro using a network cable.
Table 5-13 Default IP addresses for the WAN and LAN ports on the ECC800-Pro
Port
WAN1
WAN2
LAN1 and LAN2
● In ECC800 V100R002C10 and earlier versions, the default IP address for the
● The WAN1 port IP address cannot be set to an IP address in any of the
● IP addresses for the WAN1 and WAN2 ports should not be set in the same
● In some customized scenarios, the default IP address for the WAN2 port is
● The WAN port supports Internet access, and the LAN port supports LAN access.
Issue 03 (2021-07-15)
If the connection fails, check whether the cable is properly connected to
the device, whether the device is running properly, and whether the
parameter settings are consistent with the device parameters.
Supported operating system: Windows 7 and later versions
Recommended screen resolution: 1366 x 768 or higher
Browser: Chrome, Firefox, Internet Explorer 11 or later
NO TICE
WAN1 port is 192.168.1.10.
following network segments: 192.168.0.x, 192.168.245.x, 192.168.246.x and
192.168.248.x.
network segment.
192.168.248.10. The default value may vary.
Connect the PC network port to the WAN port or LAN port on the ECC800-Pro
based on the access network.
Copyright © Huawei Technologies Co., Ltd.
Default IP Address
192.168.8.10
192.168.0.10
192.168.248.10
5 Power-On Commissioning