Step 5 Switch on the upstream input circuit breaker (UPS output circuit breaker outside
the smart module) for the precision PDF to power on the precision PDF.
If the Power indicator on the front panel of the precision PDF lights up, the precision PDF is
powered on properly.
1.
2.
3.
Issue 03 (2021-07-15)
NO TE
Check that the voltage and frequency are within the normal ranges.
NO TE
– Measure the line voltage at the customer input side using a multimeter. The line
voltage should be in the range of 342–456 V.
– Measure the frequency at the customer input side using a multimeter. In the 50 Hz
scenario, the frequency should be in the range of 47–53 Hz. In the 60 Hz scenario, the
frequency should be in the range of 57-63 Hz.
Wait 2 to 3 minutes until the MDU screen starts. Then log in to the system.
NO TICE
– Check that the MDU screen displays information properly and
communicates properly.
– After the first login, change the password in time to improve account
security and prevent unauthorized network attacks, such as data
tampering. Huawei will not be liable for any security issues caused by your
failure to change the preset password in time or password loss after
changing.
Table 5-9 Initial passwords
System User
admin (system administrator)
operator (common user)
Perform quick settings.
Table 5-10 Settings Wizard
Item
Parameter
Language
-
Data and
Date format
Time
YYYY-MM-DD
Time zone
Time (H:M:S)
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Initial Password
000001
000001
Setting
Set as required.
Set as required.
Actual date
Actual time zone
Actual time