Huawei FusionModule2000-S User Manual page 241

Smart modular data center
Hide thumbs Also See for FusionModule2000-S:
Table of Contents

Advertisement

FusionModule2000-S Smart Modular Data Center
User Manual
Table 6-10 Semiannual maintenance for the management system
Maintenanc
e Item
Availability
of the smart
ETH gateway
Availability
of the
cabinet
electronic
lock
Issue 03 (2021-07-15)
Method
On the ECC800-
Pro WebUI,
choose
Monitoring >
System > Smart
ETH Gateway
Group > Smart
ETH Gateway.
On the Running
Info page, view
the
communication
status, PoE port
connection, and
power supply
status.
Observe the
cabinet electronic
lock indicator and
check the lock
function by
swiping a card.
Copyright © Huawei Technologies Co., Ltd.
6 Operation and Maintenance
Expected Result
The connection
status and power
supply status of the
PoE port on the
smart ETH gateway
can be queried on
the ECC800-Pro
WebUI.
After the card is
swiped, the green
indicator is on and
the door lock is
open.
Troubleshooting
If the display is
abnormal, check
whether the
communications
cable is loose or
disconnected. If so,
reconnect the cable.
If not, replace the
smart ETH gateway.
If the door is
abnormal, replace the
access card. If the
door can be opened
after the access card
is replaced, record
the access card again.
If the door still
cannot be opened,
check the cable
connection and
power supply of the
cabinet electronic
lock. If the cable
connection and
power supply are
abnormal, replace the
cabinet electronic
lock.
232

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r021c10

Table of Contents