Step 3 Turn on the circuit breakers of the ATS operation mechanism (Q1 and Q2 in the
left lower part at the rear of the cabinet) to power on the ATS operation
mechanism.
Step 4 Check whether the controller has alarms. If an alarm exists, rectify the fault first.
Step 5 Press the locking latch on the ATS panel, pull out the handle, and insert it into the
slot.
Step 6 Check the ATS Motor/Manual selection lever, and flip it to the Motor mode.
Step 7 Check the AC input and configuration status of the ATS.
After the AC input is normal, the ATS controller starts. Check and set ATS
parameters based on the AC input parameters.
Issue 03 (2021-07-15)
NO TE
● A password is required to log in to the configurations page. Set the password by using
the Up, Down, and Enter buttons. The initial password is 0001.
● Language setting: Default screen > Main Menu > Device Configuration > Language.
On the default screen, hold down
On the main menu screen, select system configuration and press
The following table lists the system configuration attributes and values.
Table 5-1 System configuration attributes and values
Item
Rated operating
voltage
Rated frequency
Number of Phases
LN1
Number of Phases
LN2
Secondary load
Copyright © Huawei Technologies Co., Ltd.
. The main menu screen is displayed.
Value
110 V/57 V; 115 V/66 V; 120
V/70 V; 208 V/120 V; 220
V/127 V; 230 V/132 V; 240
V/138 V; 227 V/160 V; 347
V/200 V; 380 V/220 V; 400
V/230 V; 415 V/240 V; 440
V/254 V; 480 V/277 V
50 Hz; 60 Hz
Single phase; three-phase
four-wire; three-phase
three-wire
Single phase; three-phase
four-wire; three-phase
three-wire
Not Used; Opening Only;
Opening And Closing
5 Power-On Commissioning
Description
The default value is
380 V/220 V. Set the
parameter based on
site requirements.
The default value is 50
Hz. Set the parameter
based on site
requirements.
The default value is
three-phase four-wire.
The default value is
three-phase four-wire.
The default value is
Not Used.
.
120