Step 2 Mount the T/H sensor onto the secured base.
Figure 3-107 Installing a T/H sensor (rear door)
Step 3 Set device addresses for the T/H sensors.
Issue 03 (2021-07-15)
NO TE
● The T/H sensor can be installed between the 33 U and 40 U positions based on site
requirements.
● Install the front-door T/H sensor on the left door post, and the rear-door T/H sensor on
the right door post.
NO TE
Secure the T/H sensors inside the cabinet at the return air side of the smart cooling product
and connect their IN ports to the main control board. When connecting the T/H sensors
outside the cabinet, connect the OUT port of one T/H sensor inside the cabinet to the IN
port of the next T/H sensor outside the cabinet. Connect all T/H sensors in series in this
way.