FusionModule2000-S Smart Modular Data Center
User Manual
Item
Copper bar
overtemperature
Abnormal
pressure of fire
gas cylinder
Battery
overcurrent
(discharge)
Battery
overtemperature
Step 4 After the green indicator of the BCU blinks at super short intervals, switch on the
battery circuit breaker on the SmartLi.
Step 5 When multiple SmartLi cabinets are combined:
1.
2.
----End
Issue 03 (2021-07-15)
Description
If this parameter is set to
Enable, an alarm is
reported when the copper
bar is overheated.
If this parameter is set to
Enable, an alarm is
reported when the fire
cylinder pressure is
abnormal.
If this parameter is set to
Disable, no alarm is
reported when battery
overcurrent occurs during
discharging.
If this parameter is set to
Enable, an alarm is
reported when battery
overcurrent occurs during
discharging.
If this parameter is set to
Disable, no alarm is
reported when battery
overtemperature occurs.
If this parameter is set to
Enable, an alarm is
reported when battery
overtemperature occurs.
If the green indicator of one BCU blinks at super short intervals, switch on the
battery circuit breaker on any SmartLi. In this case, the green indicators of all
BCUs blink intermittently, and you cannot switch on the battery circuit
breakers on other SmartLi cabinets or start the UPS in cold mode.
Wait for about 15s. After the green indicators of other BCUs blink at super
short intervals, switch on the battery circuit breaker on the SmartLi where the
BCU blinks at super short intervals one by one.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Default
Value Range
Value
Enable
Disable, Enable
Enable
Disable, Enable
Disable
Disable, Enable
Disable
Disable, Enable