Huawei FusionModule2000-S User Manual page 174

Smart modular data center
Hide thumbs Also See for FusionModule2000-S:
Table of Contents

Advertisement

FusionModule2000-S Smart Modular Data Center
User Manual
DIP switch 8 is used to switch the temperature display mode. The device address is
set in binary mode. 1 is the least significant bit, and 6 is the most significant bit.
ON indicates 1, and OFF indicates 0. The address range is 1 to 4.
Figure 5-21 DIP switch definitions for T/H sensors
Table 5-24 T/H sensor DIP switch
T/H Sensor
Address
1
2
3
4
Step 2 Add a T/H sensor.
1.
2.
Issue 03 (2021-07-15)
NO TE
The numbers 1–4 indicate the DIP switch settings of the T/H sensors.
DIP
DIP
Switc
Switc
h 1
h 2
ON
OFF
OFF
ON
ON
ON
OFF
OFF
Log in to the ECC800-Pro WebUI as an administrator.
a.
Log in to the ECC800-Pro WebUI as an administrator.
b.
Choose System Settings > Signal Name Modify. The Batch Signal
Configuration page is displayed.
c.
Set Device type to ECC800, set Device name to ECC800, and click OK.
d.
On the query result tab page, set the new signal name of COM3 to T/H
Sensor and click Submit.
e.
Choose Monitoring > System > ECC800 > Running Parameters > COM3
Port Settings.
f.
Set T/H sensor to Enable and click Submit.
g.
The T/H sensor type is automatically identified as T/H sensor.
h.
Click Unhide All Advanced Signals, then click Power Supply
Parameters. Ensure that I power supply enable(AIDI_3/COM1/AIDI_4/
COM3) is Enable.
Add a T/H sensor.
Copyright © Huawei Technologies Co., Ltd.
DIP
DIP
DIP
Switc
Switc
Switc
h 3
h 4
h 5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
5 Power-On Commissioning
DIP
DIP
DIP
Switc
Switc
Switc
h 6
h 7
h 8
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
165

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r021c10

Table of Contents